User Settings

Table 3-3Generator Configuration Settings, Values, Defaults, and User Settings

 

 

 

User

Setting

Values

Default

Setting

 

 

 

 

Generator Menu Items:

 

 

 

 

 

 

“Starter Cool Down”

1s to 250s (increments of 1s)

60s

 

 

 

 

 

“Gen Cool Down”

0s to 90 s (increments of 1s)

30s

 

 

 

 

 

“Max Run Time”

0hours–24 hours

8hours

 

 

 

 

 

“Exercise Per”

0days (Off)–250days

21days

 

 

 

 

 

“Exercise Dur”

1min–250min

30min

 

 

 

 

 

“Exercise Time”

12:00AM–11:59PM (12-hour clock)

9:00AM (12-hour clock)

 

 

00:00–23:59 (24-hour clock)

9:00 (24-hour clock)

 

 

 

 

 

“Relay3”

Preheat, WrmupCoolDn, Preheat

NotUsed

 

 

SDByp, NotUsed

 

 

 

 

 

 

“Gen Run Hold

0.5s to 20s (increments of 1s)

0.5s

 

Time”

 

 

 

 

 

 

 

“Crank Delay”

0s to 60s (increments of 1s)

0s

 

 

 

 

 

“Crank Time”

0s to 250s (increments of 1s)

30s

 

 

 

 

 

“Crank Retry Time”

0s to 250s (increments of 1s)

40s

 

 

 

 

 

“Preheat Time”

0s to 250s (increments of 1s)

0s

 

 

 

 

 

“Gen Start Tries”

1 to 10

3

 

 

 

 

 

Multi-Unit Configuration:

 

 

 

 

 

 

“Dev Name”

1-15 characters

XW AGS

 

 

 

 

 

“Dev Number”

00 to 31

00

 

 

 

 

 

Connections:

 

 

 

 

 

 

 

“DC Conn”

None, HouseBatt1 to 6,

HouseBatt1

 

 

StartBatt1 to 6

 

 

 

 

 

 

“AC In”

None, Grid1to 10, Gen1 to 10

Grid1

 

 

 

 

 

“AC Out”

None, ACLoad1 to 10

ACLoad1

 

 

 

 

 

“Generator”

Gen1 to 10

Gen1

 

 

 

 

 

975-0307-01-01