EXCEL 10 W7761A INPUT/OUTPUT DEVICE

Make earth ground connections with the shortest possible wire run using 14 AWG (2.0 mm2) wire. A good earth ground is essential for W7761A operation. Ideally, connect the earth ground to the ground bus at a motor control center or circuit breaker panel. However, if the nearest ideal earth ground is inaccessible, consider an alternate source for earth ground. Metal water pipe is generally a good ground, but do not use sprinkler pipe if prohibited by local codes. Attention must be given when duct work, conduit, or rebar are to be considered as ground sources. It is the responsibility of the installer to assure that these structures are tied back to a known earth ground.

Step 4. Prepare Wiring Diagrams

General Considerations

The purpose of this step is to assist the application engineer in developing job drawings to meet job specifications. Wiring details are included for the W7761A device the T7770A,B,C,D wall module (sensor—current feature that can be used with the RIO Device) and the T7780 DDWM. The drawings detail I/O, power, and communication bus wiring connections.

NOTE: For field wiring, when two or more wires are to be attached to the same connector block terminal, be sure to twist them together. Deviation from this rule can result in improper electrical contact. See Fig. 15.

The connector block terminals on the W7761A and on the T7770 accept 14 through 22 AWG (2.0 to 0.34 mm2) wire. Table 6 lists wiring types, sizes, and length restrictions for Excel 10 products.

Table 6 . Field Wiring Reference Table.

Wire

Recommended

 

Specification

 

 

Minimum Wire

 

or

 

Maximum Length

Function

Size AWG (mm2)

Construction

Requirement

Vendor Wire Type

ft (m)

E-Bus

22 AWG

Twisted pair solid conductor,

Level IV 140°F

Honeywell

Refer to E-Bus

(Plenum)

(0.34 mm2)

nonshielded or Echelon®

(60°C) rating

AK3791 (one twisted pair)

Wiring Guidelines

 

 

approved shielded cable.

 

AK3792 (two twisted pairs)

for maximum

 

 

 

 

 

length

 

 

 

 

 

 

E-Bus

22 AWG

Twisted pair solid conductor,

Level IV 140°F

Honeywell

Refer to E-Bus

(Non-

(0.34 mm2)

nonshielded or Echelon®

(60°C) rating

AK3781 (one twisted pair)

Wiring Guidelines

Plenum)

 

approved shielded cable.

 

AK3782 (two twisted pairs)

for maximum

 

 

 

 

 

length

 

 

 

 

 

 

Input

18 to 22 AWG

Multiconductor (usually five-

140°F (60°C)

Standard thermostat wire

1000 ft (305m)

Wiring

(1.0 to 0.34 mm2)

wire cable bundle). For runs

rating

 

for 18 AWG

Sensors

 

>200 ft (61m) in noisy EMI

 

 

200 ft (61m)

Contacts

 

areas, use shielded cable.

 

 

for 22 AWG

 

 

 

 

 

 

Output

14 AWG (2.0

Any pair nonshielded (use

NEC Class 2

Honeywell

Limited by line-loss

Wiring

mm2)

heavier wire for longer

140°F (60°C)

AK3702 (18 AWG)

effects on power

Actuators

(18 AWG (1.0

runs).

rating

AK3712 (16 AWG)

consumption.

Relays

mm2) acceptable

 

 

AK3754 (14 AWG)

(See Line Loss

 

for short runs)

 

 

or equivalent

subsection.)

 

 

 

 

 

 

Power

14 AWG

Any pair nonshielded (use

NEC Class 2

Honeywell

Limited by line-loss

Wiring

(2.0 mm2)

heavier wire for longer

140°F (60°C)

AK3754 (14 AWG)

effects on power

 

 

runs).

rating

twisted pair

consumption.

 

 

 

 

AK3909 (14 AWG) single

(See Line Loss

 

 

 

 

conductor or equivalent

subsection.)

 

 

 

 

 

 

W7761A Devices

Fig. 16 through 20 illustrate W7761A Device wiring for various configurations. Connections to the wall module terminals (4 through 6) and the communications terminals (14 and 15) are made at terminal blocks. Connection for access to the E-Bus is provided by plugging the connector into the communications jack.

NOTE: If an Excel 10 W7761A Device or Zone Manager is not connected to a good earth ground, the device internal transient protection circuitry is compromised and the function of protecting the device from noise and power line spikes cannot be fulfilled. This can result in a damaged circuit board and require replacing the device.

24

74-2699

Page 24
Image 24
Honeywell specifications Prepare Wiring Diagrams, General Considerations, W7761A Devices