36
Fig. 23. Temperature sensor resistance plots.
Alarms
When an Excel 10 has an alarm condition, it reports it to the central node on the E-Bus (typically, the Excel 10 Zone Manager). See Table 9. Information contained in an alarm message is:
Subnet Number:
E-Bus subnet that contains the Excel 10 node that has the alarm condition. Subnet 1 is on the Zone Manager side of the router; Subnet 2 is on the other side.
Node Number:
Excel 10 node that has the alarm condition (see Network Status). Alarm Type:
Specific alarm being issued. An Excel 10 can provide the alarm types listed in Table 9.
20K
10K
60K
50K
40K
30K
RESISTANCE (OHMS)
Step 6. Configure Devices
Excel E-Vision PC Software is used to configure W7761A Devices to match their intended application. The E-Vision User Guide form, 74-2588 provides details for operating the PC software.
Step 7. Troubleshooting
Troubleshooting Excel 10 Controllers and Wall Modules
In addition to the following information, refer to the Installation Instructions and Checkout and Test manual for each product. See the Applicable Literature section for form numbers.
Temperature Sensor and Setpoint Potentiometer Resistance Ranges
The T7770 Wall Module or the C7770A Air Temperature Sensor has the following specified calibration points, which are plotted in Fig. 23:
Temperature (°F)Resistance Value (ohms)
9911,520
8516,301
7024,039
5536,280
4548,000
80K
70K
20K OHM AT
77oF (25oC)

 

 

 

 

EXCEL 10 W7761A INPUT/OUTPUT DEVICE

 

 

 

 

 

 

 

Table 8. Excel 10 W7761A Device Ordering Information (Continued).

 

 

 

 

 

 

 

 

Part Number

 

 

Product Description

 

Comments

 

 

 

 

 

 

 

 

 

 

 

Cabling (Continued):

 

 

 

 

 

 

 

 

 

Honeywell AK3752

 

Outputs/Power: 14 to 18 AWG (2.0 to 1.0 mm2)

 

NEC Class 2 140°F (60°C) rating

 

(typical or equivalent)

 

 

 

 

 

 

 

 

 

 

 

 

 

Honeywell AK3702

 

18

AWG (1.0 mm2) twisted pair

 

Non-plenum

 

(typical or equivalent)

 

 

 

 

 

 

 

 

 

 

 

 

 

Honeywell AK3712

 

16

AWG (1.3 mm2) twisted pair

 

Non-plenum

 

(typical or equivalent)

 

 

 

 

 

 

 

 

 

 

 

 

 

Honeywell AK3754

 

14

AWG (2.0 mm2) two conductor

 

Non-plenum

 

(typical or equivalent)

 

 

 

 

 

 

 

 

 

 

 

 

 

30

40 50

60 70 80

90

100 110 oF

0

10

20

30

40 oC

 

TEMPERATURE (DEGREES)

M5874A

74-2699

Page 36
Image 36
Honeywell W7761A specifications Temperature Degrees