EXCEL 10 W7761A INPUT/OUTPUT DEVICE

Voltage to A/D

Sensor Voltage

 

 

0.00

0.00

 

 

0.50

0.25

 

 

1.00

0.50

 

 

1.50

0.75

 

 

2.00

1.00

 

 

2.50

1.25

 

 

3.00

1.50

 

 

3.50

1.75

 

 

4.00

2.00

 

 

4.50

2.25

 

 

5.00

2.50

 

 

5.50

2.75

 

 

6.00

3.00

 

 

6.50

3.25

 

 

7.00

3.50

 

 

7.50

3.75

 

 

8.00

4.00

 

 

8.50

4.25

 

 

9.00

4.50

 

 

9.50

4.75

 

 

10.00

5.00

 

 

A/D VOLTS

SENSOR VOLTAGE VERSUS INPUT VOLTAGE TO A/D

5.00

4.50

4.00

3.50

3.00

2.50

2.00

1.50

1.00

0.50

0

0

100

200

300

400

500

600

700

800

900

1000

 

 

 

 

 

VOLTS

 

 

 

M11612

Fig. E-10. Graph of Sensor Voltage versus input Voltage to A/D.

Sensor Type:

Third party.

Sensor Use:

Sensor Voltage (Vdc)/Pressure Inw (kPa) 2 to 10V, 0 to 5 inw (0 to 1.25 kPa).

Table E-11 lists the points for Sensor Voltage (Vdc) versus Pressure (Inw). Fig. E-11 shows the graph of these points.

 

 

Table E-11. Sensor Voltage (Vdc) Versus Pressure (Inw).

 

 

 

Pressure Inw (kPa)

Sensor Voltage (Vdc)

 

 

 

 

 

0.00

(0.00)

2.00

 

 

 

 

0.50.(0.13)

2.80

 

 

 

 

 

1.00

(0.25)

3.60

 

 

 

 

 

1.50

(0.37)

4.40

 

 

 

 

 

2.00

(0.5)

5.20

 

 

 

 

 

2.50

(0.62)

6.00

 

 

 

 

 

79