EXCEL 10 W7761A INPUT/OUTPUT DEVICE

Appendix C. Complete List of Excel 10 W7761A Remote I/O Device User Addresses.

C1. Input/Output Points.

C2. Control Parameters.

C3. Status Points.

C4. Configuration Parameters.

C5. Direct Access And Special Points.

Table C0 lists the applicable Engineering Units for the analog points found in the W7761A.

Table C0. Engineering Units For Analog Points.

 

English Units (Inch-Pound)

Standard International Units (SI)

 

 

 

 

 

Measured Item

Description

Abbreviation

Description

Abbreviation

 

 

 

 

 

Temperature

Degrees Fahrenheit

F

Degrees Celsius

C

 

 

 

 

 

Relative

Delta Degrees Fahrenheit

DDF

Degrees Kelvin

K

Temperature

 

 

 

 

 

 

 

 

 

Relative Humidity

Percent

%

Percent

%

 

 

 

 

 

Air Flow

Cubic Feet per Minute

CFM

Meters cubed per hour

m3h

 

 

 

 

 

CO2 Concentration

Parts Per Million

PPM

Parts Per Million

PPM

Enthalpy

British Thermal Units per Pound

btu/lb

kiloJoules/kilogram

kJ/kg

 

of Air

 

 

 

 

 

 

 

 

Differential

Inches of Water Column

inw

kiloPascal

kPa

Pressure

 

 

 

 

 

 

 

 

 

Tables C1 through C5 list all network variables associated with the W7761A Controller and the default User Address names. Table C1 lists the Network Variable Inputs and Outputs, which are stored in RAM memory. Table C2 lists the Control Parameters, which are the values stored in the controllers EEPROM memory.

NOTE: Table C2. User Addresses For W7761A Control Parameters. (Control Parameters are stored in EEPROM - limited to 10,000 writes. Do NOT use as outputs from Control Strategies, Time Programs, or Switching Tables. If these points are changed more than 10,000 times, irreversible hardware failure results).

Tables provides point attributes as follows:

Engineering

 

Units—

This field indicates the point valid range and displayed Engineering Unit. For digital points, the valid states

 

and the corresponding enumerated values are shown.

Default—

The value or state of the point on controller start-up.

Shareable— The point can be set up for data sharing in Command Multiple Points, Read Multiple Points, or Refer Excel 10 Points as either a data source or a destination.

Mappable—

The point can be converted into a C-Bus point used by C-Bus devices. A mappable point has a one-to-one

Direct

relationship with a C-Bus User Address.

 

Access—

The point is accessible through the Subsystem Points mechanism in XBS.

E-Vision

 

Monitor—

These points are viewable within the E-Vision Controller Monitoring on-line screen. PAR refers to control

Hardware

parameters that are set in the Application Selection dialog boxes in E-Vision.

 

Config—

These are points that involve controller I/O configuration. Any change to HW Config. points causes the

 

W7761A to perform an application reset; therefore, these points can only be modified off-line.

Manual—

These points are used to set the controller outputs when in manual mode. The W7761A is placed in manual

 

mode through a menu selection in the E-Vision Controller Monitor screen.

Fixable—

These input points can be set to a constant value in the E-Vision Controller Monitor screen.

NOTES:

1.Mapped points can be viewed and changed, if applicable, on C-Bus devices such as an XI581, XI582 and XI584 and on an XBS central and E-Vision.

2.All Excel 10 points, mappable, calibration, configuration and internal data sharing points, can be viewed and changed, as allowed, via Direct Access (DA) mode in the XBS subsystem menu or via XI584.

3.E-Vision - These points are displayed to the user and polled during the E-Vision monitor function. Monitor (M) indicates the point appears in the Software list box. Schematic (S) indicates the point is to be displayed on the schematic air handler diagram directly. Calibrate (C) - These points are calibratible and the calibration dialog (either the temperature or air flow dialog) is displayed. These points are displayed in a listbox by selection of the menu item Controller, Calibration. When the user double clicks on these points the calibration dialog is displayed. Parameter (P) - This information is displayed to the user in the Application Selection screens. These fields are read/write when offline and read only when online.

4.Manual - These points can be placed in the manual mode. When the user double clicks on these points the manual dialog is displayed, this contains radio buttons; one for Auto and one for Manual.

44

74-2699

Page 44
Image 44
Honeywell W7761A Temperature Relative Humidity, Air Flow, CO 2 Concentration, Enthalpy, Differential, Pressure