EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Appendix C. Complete List of Excel 10 W7761A Remote I/O Device User Addresses.
C1. Input/Output Points.
C2. Control Parameters.
C3. Status Points.
C4. Configuration Parameters.
C5. Direct Access And Special Points.
Table C0 lists the applicable Engineering Units for the analog points found in the W7761A.
Table C0. Engineering Units For Analog Points.
| English Units | Standard International Units (SI) | ||
|
|
|
|
|
Measured Item | Description | Abbreviation | Description | Abbreviation |
|
|
|
|
|
Temperature | Degrees Fahrenheit | F | Degrees Celsius | C |
|
|
|
|
|
Relative | Delta Degrees Fahrenheit | DDF | Degrees Kelvin | K |
Temperature |
|
|
|
|
|
|
|
|
|
Relative Humidity | Percent | % | Percent | % |
|
|
|
|
|
Air Flow | Cubic Feet per Minute | CFM | Meters cubed per hour | m3h |
|
|
|
|
|
CO2 Concentration | Parts Per Million | PPM | Parts Per Million | PPM |
Enthalpy | British Thermal Units per Pound | btu/lb | kiloJoules/kilogram | kJ/kg |
| of Air |
|
|
|
|
|
|
|
|
Differential | Inches of Water Column | inw | kiloPascal | kPa |
Pressure |
|
|
|
|
|
|
|
|
|
Tables C1 through C5 list all network variables associated with the W7761A Controller and the default User Address names. Table C1 lists the Network Variable Inputs and Outputs, which are stored in RAM memory. Table C2 lists the Control Parameters, which are the values stored in the controllers EEPROM memory.
NOTE: Table C2. User Addresses For W7761A Control Parameters. (Control Parameters are stored in EEPROM - limited to 10,000 writes. Do NOT use as outputs from Control Strategies, Time Programs, or Switching Tables. If these points are changed more than 10,000 times, irreversible hardware failure results).
Tables provides point attributes as follows:
Engineering |
|
Units— | This field indicates the point valid range and displayed Engineering Unit. For digital points, the valid states |
| and the corresponding enumerated values are shown. |
Default— | The value or state of the point on controller |
Shareable— The point can be set up for data sharing in Command Multiple Points, Read Multiple Points, or Refer Excel 10 Points as either a data source or a destination.
Mappable— | The point can be converted into a |
Direct | relationship with a |
| |
Access— | The point is accessible through the Subsystem Points mechanism in XBS. |
| |
Monitor— | These points are viewable within the |
Hardware | parameters that are set in the Application Selection dialog boxes in |
| |
Config— | These are points that involve controller I/O configuration. Any change to HW Config. points causes the |
| W7761A to perform an application reset; therefore, these points can only be modified |
Manual— | These points are used to set the controller outputs when in manual mode. The W7761A is placed in manual |
| mode through a menu selection in the |
Fixable— | These input points can be set to a constant value in the |
NOTES:
1.Mapped points can be viewed and changed, if applicable, on
2.All Excel 10 points, mappable, calibration, configuration and internal data sharing points, can be viewed and changed, as allowed, via Direct Access (DA) mode in the XBS subsystem menu or via XI584.
3.
4.Manual - These points can be placed in the manual mode. When the user double clicks on these points the manual dialog is displayed, this contains radio buttons; one for Auto and one for Manual.
44 |