EXCEL 10 W7761A INPUT/OUTPUT DEVICE

displayed. Select the project and the Zone manager within that project that is being exported and the Export button. Exit CARE and Start E-Vision. Select the E-Vision project to open and the CARE Export Filename created previously. Once the project is open, select the RIO device that the Digital Output is connected to and go into the Application Selection screen (offline) by selecting the Controller, Application Selection menu items. From the Outputs tab of the Application Selection dialog box, select the first Unused_DigOutput and scroll up until Discrete1 is displayed and select it. Select the OK button to save the selection.

4.Select the Controller menu item and then Import from CARE to import the Zone Manager files with the new pseudo analog point. If this function has already been performed before, the user will be prompted with the message CARE Export File has already been imported, do you want to import again?. Select Yes to continue with the Import. When the import is finished, E-Vision displays the message CARE Export File has been imported. Select OK to continue.

5.Select the Network menu item and then Map C-Bus Points. Select RIO1 as the Controller Type from the Map C-Bus Points dialog box. Under Unmapped CARE, select the name of the RIO device that the Digital Output was added to in CARE. Under Unmapped Excel 10, select the name of the RIO device that the actual Digital Output was added to (both names should be the same). Next, select the Custom button and the Custom Mapping CARE Points dialog box will be displayed. Select the MiscExhFan point under CARE Points and DigOut1Cmd under Excel 10. Select the Map button to add the MiscExhFan point to the list of Mapped Points. Click on the Close button to exit the Custom Mapping CARE Points dialog box. Click on the Close button to exit the Map C-Bus Points dialog box.

6.Re-commission the RIO device that had the custom mapping done.

7.Select the Controller menu item and the Update Zone Manager Files. E-Vision will add the custom mapping information to the Zone Manager files. When the Update Zone Manager Files function is done, close the E-Vision project and exit out of E-Vision.

8.Start CARE and open the Zone Manager that was just updated through the Update Zone Manager Files function and start XI584 by selecting the Controller, Tools and XI584 menu items. Once XI584 is started, select the Utilities, File Transfer menu items and select CARE Import. Select the project and the Zone Manager that was just updated and select Import and click OK on the Select Target Controller dialog box. When the CARE Import is complete, close the CARE Import dialog box. If this is the initial loading of the Zone Manager, then it will have to be reset and the CPU address set by the XI581 Emulation function (Applications, XI581 Emulation menu). Select the Utilities, File Transfer menu items and select Download. The Download dialog box will be displayed. Check the All selection and click the Controller button. When the Select Controller/Subsystem dialog box is displayed, make sure that the correct CPU address or name is highlighted and select the OK button. Click the Download button and Yes to the message Replace updated application part in controller (CPU address or Controller name). When the download is complete, exit out of the Download dialog box. From the XI584 main menu, select the Data, Access by User Address menu items. Type MiscExhFan in the Search For User Address and click on the Search button. When the MiscExhFan point displays in the User Addresses list, click on the point and select the Attributes button. XI584 will now display the value of the Digital Output connected to the RIO device. To command the MiscExhFan to the On mode, put the point in the Manual mode and enter a value of 1.0 or greater. To command the MiscExhFan to the Off mode, put the point in the Manual mode and enter a value of 0.0. This point can now be used in the Zone Manager control strategy or switching logic and Time Programs. This point can be used in other Excel 5000 controllers (C-Bus) by assigning a global analog point in the destination controller with the user address name of MiscExhFan. Refer to the CARE User’s Manual form, 74-5587 for information on creating global points in Excel 5000 controllers.

Table A-3. Supported Digital Output Types.

E-Vision Enumerated Name in the Output

RIO Network Variable that contains the

Application Selection Tab

Hardware Output Value

 

 

Float1_Open through Float8_Open (Series 60 -

DigOut1Cmd through DigOut8Cmd

requires two outputs assigned. Float1_Open

 

must be assigned before Float1_Close)

 

 

 

Float1_Close through Float8_Close (Series 60

DigOut1Cmd through DigOut8Cmd

- requires two outputs assigned. Float1_Open

 

must be assigned before Float1_Close)

 

 

 

Discrete1 through Discrete8 (Maintained On/Off

DigOut1Cmd through DigOut8Cmd

outputs)

 

 

 

Modulate1 through Modulate8 (PWM outputs)

DigOut1Cmd through DigOut8Cmd

 

 

Appendix B. Sequences of Operation.

Common Operations

The Excel 10 W7761A Device contains inputs and outputs, but no control software. All control that would be associated with the inputs and outputs in the W7761A would be accomplished though the Excel Zone Manager and would not be suitable for VAV control, temperature control, or any control function that would require less than a 30 second update rate. The analog and digital sensors could be shared or bound to other Excel 10 controllers on the E-Bus or Excel 5000 controllers on the C-Bus through the Excel 10 Zone Manager. This would allow the other Excel 10 controllers to use their physical inputs for monitoring other elements such as return humidity, IAQ, etc. to achieve better control.

Room Temperature Sensor (RmTemp)

42

74-2699

Page 42
Image 42
Honeywell W7761A specifications Appendix B. Sequences of Operation, Common Operations, Room Temperature Sensor RmTemp