EXCEL 10 W7761A INPUT/OUTPUT DEVICE
26 74-2699

GROUND 5 Analog ground

AI-1 4 Analog Input 1 resistance

3 Not Used

2 Not Used

EGND 1 Earth Ground

See Fig. 20 to wire a pneumatic transducer to a W7761A.

12345678
E-BUS
24 VAC

W7761A

REMOTE I/O

DEVICE

1
2
1
2
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM
2
)
WITH A MINIMUM OF 18 AWG (1.O MM
2
), FOR EARTH GROUND WIRE.
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED
TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
E-BUS
E GND
GND
GND
GND
NOT USED
NOT USED
AI-1 OHM
AI-2 OHM
9101112 14 J315
31 30 29 28 27 26 25 24 23 22 21 20
24 VAC COM
E-BUS
JACK
22 VDC OUT
19 18 17 16
AI-3 OHM
AI-4 OHM
AI-6 V/mA
OUT 7
OUT 6
OUT 5
OUT 4
OUT 8
OUT 1
OUT 3
OUT 2
AI-5 V/mA
13
DI-2
DI-4
DI-1
DI-3
M15276
GND
GND
TRIAC EQUIVALENT CIRCUIT
24 VAC
+-
2
JACK FOR
E-BUS
NETWORK
ACCESS
7 69 8 54321

T7770A

WALL

MODULE

GND
SENSOR
E-BUS
E-BUS

C7770A AIR

TEMPERATURE SENSOR

Fig. 16. Typical T7770A and C7770A wiring diagram. (For note 2, refer to Fig. 15.)