EXCEL 10 W7761A INPUT/OUTPUT DEVICE

Table 8. Excel 10 W7761A Device Ordering Information (Continued).

Part Number

Product Description

Comments

 

 

 

 

Accessories (Continued):

 

ML6474A1008

Direct Coupled Actuator, 132 lb-in. torque, Series 60

 

 

 

ML6185A1000

Direct Coupled Actuator, 50 lb-in. spring return

Series 60

 

 

 

EL7680A1008

Wall Mounted Wide View Infrared Occupancy Sensor

 

 

 

EL7628A1007

Ceiling Mounted Infrared Occupancy Sensor

 

 

 

EL7611A1003,

Ultrasonic Occupancy Sensors

 

EL7612A1001

 

 

 

 

EL7630A1003,

Power Supply/Control Units for Occupancy sensors

 

EL7621A1002,

 

EL7621A1010

 

 

 

 

 

C7400A1004

Solid State Enthalpy Sensor (4 to 20 mA)

For outdoor and return air enthalpy

 

 

 

C7600B1000

Solid State Humidity Sensor (2 to 10 V)

For outdoor and return air humidity

 

 

 

C7600C1008

Solid State Humidity Sensor (4 to 20 mA)

For outdoor and return air humidity

 

 

 

C7600C1018

Solid State Humidity Sensor (2 to 10 V)

For outdoor and return air humidity

 

 

 

MMC325-010,

Pneumatic Retrofit Transducers.

Use to control Pneumatic reheat valves

MMC325-020

Select pressure range: (010) 0 to 10 psi (68.97 kPa)

 

 

or (020) 0 to 20 psi (137.93 kPa).

 

 

 

 

MMCA530

DIN rail adapter for MMC325 Transducers

 

 

 

MMCA540

Metal enclosure for MMC325 Transducers

 

 

 

ML7984B3000

Valve Actuator Pulse Width Modulation (PWM)

Use with V5011 or V5013 F and G Valves

 

 

 

ML6161B1000

Damper Actuator Series 60

 

 

 

M6410A

Valve Actuator Series 60

Use with V5812/V5813 Valves

 

 

 

ML684A1025

Versadrive Valve Actuator with linkage, Series 60

Use with V5011 and V5013 Valves

 

 

 

ML6464A1009

Direct Coupled Actuator, 66 lb-in., Series 60

 

 

 

ML6474A1008

Direct Coupled Actuator, 132 lb-in. torque, Series 60

 

 

 

ML6185A1000

Direct Coupled Actuator, 50 lb-in. spring return

Series 60

 

 

 

V5812A

Two-way terminal unit water valve; 0.19, 0.29, 0.47,

Use with M6410 Valve Actuator. Close-off

 

0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm) or

rating for 0.19 to 1.9 Cv is 65 psi; for 2.9

 

2.9 and 4.9 Cv 3/4 in. npt (19 mm)

and 4.9, Cv is 45 psi. (Coefficient of

 

 

volume or capacity index Cv = gallons per

 

 

minute divided by the square root of the

 

 

pressure drop across the valve.)

 

 

 

V5813A

Three-way mixing terminal unit hot water valve; 0.19,

Use with M6410 Valve Actuator. Close-off

 

0.29, 0.47, 0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm)

rating 0.19 to 0.74 Cv is 55 psi; 1.2, and

 

or 2.9 and 4.9 Cv 3/4 in. npt (19 mm)

1.9 Cv is 22 psi; 2.9 and 4.9 Cv is 26 psi.

R8242A

Contactor, 24 Vac coil, DPDT

 

 

 

AT72D, AT88A, AK3310, etc.

Transformers

 

 

 

EN 50 022

DIN rail 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.)

Obtain locally: A controller requires 5 in.

 

 

 

Augat Inc. part number 2TK2D DIN rail (adapter)

Purchase from Augat Inc. two DIN rail

 

 

adapters for each controller

 

 

 

Serial Interface Cable, male DB-9 to female DB-9 or

Obtain locally from any computer

 

female DB-25.

hardware vendor.

 

 

 

Cabling

Honeywell AK3791 (one

E-Bus (plenum): 22 AWG (0.34 mm2) twisted pair

Level IV 140°F (60°C) rating

twisted pair) AK3792 (two

solid conductor, nonshielded or Echelon® approved

 

twisted pairs)

cable.

 

 

 

 

Honeywell AK3781 (one

E-Bus (nonplenum): 22 AWG (0.34 mm2) twisted pair

Level IV 140°F (60°C) rating

twisted pair) AK3782 (two

solid conductor, nonshielded or Echelon® approved

 

twisted pairs)

cable.

 

 

 

 

Honeywell AK3725

Inputs: 18 AWG (1.0 mm2) five wire cable bundle

Standard thermostat wire

(continued)

35

74-2699

Page 35
Image 35
Honeywell W7761A specifications Cabling