EXCEL 10 W7761A INPUT/OUTPUT DEVICE

Table C1. Input/Output Points (Right Continued).

Share (SH), Map (MA), Direct Access (DA)

E-Vision (EV): Calibrate (C), Monitor (M),

Parameter (P), Schematic (S)

Hardware Configuration (HW),

Manual Point (MN), Test (TS)

SH

MA

DA

EV

HW

MN

TS

Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcDigIn2Sts: Refer to the description for SrcDigIn1Sts.

 

 

 

 

 

 

 

 

X

X

X

M

 

 

 

DI2State:

 

 

 

 

 

 

 

Refer to the description for DI1State.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcDigIn3Sts: Refer to the description for SrcDigIn1Sts above.

 

 

 

 

 

 

 

 

X

X

X

M

 

 

 

DI3State:

 

 

 

 

 

 

 

Refer to the description for DI1State.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcDigIn4Sts: Refer to the description for SrcDigIn1Sts above.

 

 

 

 

 

 

 

 

X

X

X

M

 

 

 

DI4State:

 

 

 

 

 

 

 

Refer to the description for DI1State.

 

 

 

 

 

 

 

 

X

X

X

M

 

 

 

SrcHumidAI5 is an output network variable corresponding to the voltage or current

 

 

 

 

 

 

 

input channel (AI5) if the selection for humidity sensor was made via ncirioIoSelect

 

 

 

 

 

 

 

for AI5.

 

 

 

 

 

 

 

 

X

X

X

M

 

 

 

SrcHumidAI6 is an output network variable corresponding to the voltage or current

 

 

 

 

 

 

 

input channel (AI6) if the selection for humidity sensor was made via ncirioIoSelect

 

 

 

 

 

 

 

for AI6.

 

 

 

 

 

 

 

 

X

X

X

M

 

 

 

SrcPressAI5 is an output network variable corresponding to the voltage or current

 

 

 

 

 

 

 

input channel (AI5) if the selection for a pressure sensor was made via

 

 

 

 

 

 

 

ncirioIoSelect for AI5.

 

 

 

 

 

 

 

 

X

X

X

M

 

 

 

SrcPressAI6 is an output network variable corresponding to the voltage or current

 

 

 

 

 

 

 

input channel (AI6) if the selection for a pressure sensor was made via

 

 

 

 

 

 

 

ncirioIoSelect for AI6.

 

 

 

 

 

 

 

 

X

X

X

M

 

 

 

SrcTempAI1 is an output network variable corresponding to the analog input

 

 

 

 

 

 

 

channel (AI1). This NV will contain AI1 temperature value with the OffsetCal1AI1

 

 

 

 

 

 

 

applied to it.

 

 

 

 

 

 

 

 

X

X

X

M

 

 

 

SrcTempAI2 is an output network variable corresponding to the analog input

 

 

 

 

 

 

 

channel (AI2). This NV will contain AI2 temperature value with the OffsetCal1AI2

 

 

 

 

 

 

 

applied to it.

 

 

 

 

 

 

 

 

X

X

X

M

 

 

 

SrcTempAI3 is an output network variable corresponding to the analog input

 

 

 

 

 

 

 

channel (AI3). This NV will contain AI3 temperature value with the OffsetCal1AI3

 

 

 

 

 

 

 

applied to it.

 

 

 

 

 

 

 

 

X

X

X

M

 

 

 

SrcTempAI4 is an output network variable corresponding to the analog input

 

 

 

 

 

 

 

channel (AI4). This NV will contain AI4 temperature value with the OffsetCal1AI4

 

 

 

 

 

 

 

applied to it.

 

 

 

 

 

 

 

 

X

X

X

M

 

 

 

SrcVoltageAI is an output network variable corresponding to the voltage or current

 

 

 

 

 

 

 

input channel (AI5 or AI6) if the selection for a voltage sensor was made via

 

 

 

 

 

 

 

ncirioIoSelect.

 

 

 

 

 

 

 

 

54

74-2699

Page 54
Image 54