EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C5. Direct Access And Special Points (Left).
|
|
|
| Digital |
|
|
|
|
| State |
|
|
|
|
| or |
|
|
|
| Engineering Units: | Value |
|
|
|
| English (Metric) or | of |
|
User Address | NvName | Field Name | States plus Range | State | Default |
|
|
|
|
|
|
DestManMode | nviManualMode |
| MODE_ENABLE | 0 | MODE_ENABLE |
|
|
| MODE_DISABLE | 1 |
|
|
|
| MODE_MANUAL | 2 |
|
|
|
| SUPPRESS_ALARMS | 3 |
|
|
|
| UNSUPPRESS_ALARMS | 4 |
|
|
|
|
|
|
|
Table C5. Direct Access And Special Points (Right).
Share (SH), Map (MA), Direct Access (DA) |
|
| |||||||
|
|
| |||||||
|
| Parameter (P), Schematic (S) |
|
| |||||
| Hardware Configuration (HW), |
|
| ||||||
|
| Manual Point (MN), Test (TS) |
|
| |||||
|
|
|
|
|
|
|
|
|
|
SH | MA |
| DA | EV | HW | MN |
| TS | Comments |
|
|
|
|
|
|
|
|
|
|
| X |
| X | M P |
|
|
|
| DestManMode: is an input which is used to manually set the physical outputs. |
|
|
|
|
|
|
|
|
| DestManMode remains unchanged until another mode has been commanded or an |
|
|
|
|
|
|
|
|
| application restart has been performed. The valid enumerated values are: |
|
|
|
|
|
|
|
|
| MODE_ENABLE enables the node so that the RIO controls the physical outputs as |
|
|
|
|
|
|
|
|
| the normal mode. MODE_ENABLE is the default state after power is restored or an |
|
|
|
|
|
|
|
|
| application restart occurs. If the mode was MANUAL and DestManMode is set to |
|
|
|
|
|
|
|
|
| MODE_ENABLE, the node then goes through application restart. |
|
|
|
|
|
|
|
|
| MODE_DISABLED sets the node into the DISABLED mode. The alarm |
|
|
|
|
|
|
|
|
| NODE_DISABLED is initiated, and the physical outputs are turned off. The physical |
|
|
|
|
|
|
|
|
| inputs, network variable inputs, and network variable outputs are still functioning |
|
|
|
|
|
|
|
|
| when the node is in the DISABLED mode. |
|
|
|
|
|
|
|
|
| MODE_MANUAL sets the node into the MANUAL mode. The alarm |
|
|
|
|
|
|
|
|
| NODE_DISABLED is initiated, and the physical outputs are controlled manually as |
|
|
|
|
|
|
|
|
| commanded by DestManMode. The nodes configuration variables and |
|
|
|
|
|
|
|
|
| DestManMode are used to set valves, dampers, and/or digital output to the desired |
|
|
|
|
|
|
|
|
| manual positions or state(s). The physical inputs, network variable inputs, and |
|
|
|
|
|
|
|
|
| network variable outputs are still functioning when the node is in the MANUAL mode. |
|
|
|
|
|
|
|
|
| SUPPRESS_ALARMS causes AlarmType to be set to ALARM_NOTIFY_DISABLED, |
|
|
|
|
|
|
|
|
| and AlarmTypeLog to no longer record alarms. If alarms are suppressed, |
|
|
|
|
|
|
|
|
| UNSUPPRESS_ALARMS causes AlarmType and AlarmTypeLog to be returned to |
|
|
|
|
|
|
|
|
| reporting alarms. See nvoAlarm for more details. All unspecified values are the same |
|
|
|
|
|
|
|
|
| as MODE_ENABLE. |
|
|
|
|
|
|
|
|
|
|