EXCEL 10 W7761A INPUT/OUTPUT DEVICE

Table C5. Direct Access And Special Points (Left).

 

 

 

 

Digital

 

 

 

 

 

State

 

 

 

 

 

or

 

 

 

 

Engineering Units:

Value

 

 

 

 

English (Metric) or

of

 

User Address

NvName

Field Name

States plus Range

State

Default

 

 

 

 

 

 

DestManMode

nviManualMode

 

MODE_ENABLE

0

MODE_ENABLE

 

 

 

MODE_DISABLE

1

 

 

 

 

MODE_MANUAL

2

 

 

 

 

SUPPRESS_ALARMS

3

 

 

 

 

UNSUPPRESS_ALARMS

4

 

 

 

 

 

 

 

Table C5. Direct Access And Special Points (Right).

Share (SH), Map (MA), Direct Access (DA)

 

 

 

E-Vision (EV): Calibrate (C), Monitor (M),

 

 

 

 

Parameter (P), Schematic (S)

 

 

 

Hardware Configuration (HW),

 

 

 

 

Manual Point (MN), Test (TS)

 

 

 

 

 

 

 

 

 

 

 

 

SH

MA

 

DA

EV

HW

MN

 

TS

Comments

 

 

 

 

 

 

 

 

 

 

 

X

 

X

M P

 

 

 

 

DestManMode: is an input which is used to manually set the physical outputs.

 

 

 

 

 

 

 

 

 

DestManMode remains unchanged until another mode has been commanded or an

 

 

 

 

 

 

 

 

 

application restart has been performed. The valid enumerated values are:

 

 

 

 

 

 

 

 

 

MODE_ENABLE enables the node so that the RIO controls the physical outputs as

 

 

 

 

 

 

 

 

 

the normal mode. MODE_ENABLE is the default state after power is restored or an

 

 

 

 

 

 

 

 

 

application restart occurs. If the mode was MANUAL and DestManMode is set to

 

 

 

 

 

 

 

 

 

MODE_ENABLE, the node then goes through application restart.

 

 

 

 

 

 

 

 

 

MODE_DISABLED sets the node into the DISABLED mode. The alarm

 

 

 

 

 

 

 

 

 

NODE_DISABLED is initiated, and the physical outputs are turned off. The physical

 

 

 

 

 

 

 

 

 

inputs, network variable inputs, and network variable outputs are still functioning

 

 

 

 

 

 

 

 

 

when the node is in the DISABLED mode.

 

 

 

 

 

 

 

 

 

MODE_MANUAL sets the node into the MANUAL mode. The alarm

 

 

 

 

 

 

 

 

 

NODE_DISABLED is initiated, and the physical outputs are controlled manually as

 

 

 

 

 

 

 

 

 

commanded by DestManMode. The nodes configuration variables and

 

 

 

 

 

 

 

 

 

DestManMode are used to set valves, dampers, and/or digital output to the desired

 

 

 

 

 

 

 

 

 

manual positions or state(s). The physical inputs, network variable inputs, and

 

 

 

 

 

 

 

 

 

network variable outputs are still functioning when the node is in the MANUAL mode.

 

 

 

 

 

 

 

 

 

SUPPRESS_ALARMS causes AlarmType to be set to ALARM_NOTIFY_DISABLED,

 

 

 

 

 

 

 

 

 

and AlarmTypeLog to no longer record alarms. If alarms are suppressed,

 

 

 

 

 

 

 

 

 

UNSUPPRESS_ALARMS causes AlarmType and AlarmTypeLog to be returned to

 

 

 

 

 

 

 

 

 

reporting alarms. See nvoAlarm for more details. All unspecified values are the same

 

 

 

 

 

 

 

 

 

as MODE_ENABLE.

 

 

 

 

 

 

 

 

 

 