9-6 Poor cooling in Fresh food section
No |
|
|
| Checking flow |
| Result & SVC Action | |||||
|
|
|
|
|
|
|
|
|
|
|
|
1 | Check the sensor resistance. |
|
|
|
|
|
| ||||
| Temperature | Result |
|
| |||||||
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 23°F / | 38 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 32°F / 0°C | 30 |
|
| |
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 41°F / 5°C | 24 |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| <CON4> |
| 50°F / 10°C | 19.5 |
|
| |||
|
|
|
|
|
|
|
|
| |||
| The sensor is determined by |
| 59°F / 15°C | 16 |
|
| |||||
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| |||||
| the temperature. |
|
|
|
|
|
| ||||
| For example, 30 indicates 32°F. |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
2 | Reset the unit and |
|
|
|
|
|
| ||||
| Input Test 1 Mode. |
|
|
|
|
|
| ||||
| (Push the button 1 time) |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
3 | Open the fresh food door and |
|
|
|
|
|
| ||||
| Status |
| SVC Action |
| |||||||
| Check the air flow. |
|
|
| |||||||
|
| Airflow |
| Go to the 4 |
| ||||||
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| No airflow | Check the R Fan motor |
| ||
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| Check the damper |
| ||
|
|
|
|
|
|
|
|
| (Go to the 6) |
| |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||
4 | Check the air temperature. |
|
|
|
|
|
| ||||
| Status |
| SVC Action |
| |||||||
| Cold or not? |
|
|
| |||||||
|
| Cold |
| Normal |
| ||||||
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Not cold | Check the Compressor |
| ||
|
|
|
|
|
|
|
| And sealed system |
| ||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
- 39 -