6-8

Freeze Mode:

30 second s have elapsed
Harvest Mode
(See page 6-9)
Unit leaves
Idle Mode
Compressor &
Condenser Fan
are energized
(30 seconds)
Compressor, Condenser
Fan, & Recirculation
Pump are energized
(15 minutes)*
Compressor, Condenser
Fan, & Recirculation
Pump continue energized
dependent on the
temperature at the
evaporator thermistor
(10 minutes max.)
Evap. at less than 6.5°F
or 10 minutes** have elapsed
15 minutes* have elapsed
**

NOTE: Control boards with Code Date MGR/0245, (45th week, 2002), and later, will allow

thickness adjustments. Use the following chart to determine the freeze time (see “Adjusting The

Ice Thickness” on page 8-3 for more information).

Jumper at P4
on electronic
control
* Minimum
freeze time
** Maximum additional
time (dependent on evap.
Thermistor temp.)
*** Total
Maximum
freeze time
Pins 4 & 5 Thick Ice 19 8 2 7
Pins 2 & 3
(factory default) Normal Ice 1 5 10 25
Pins 1 & 2 Thin Ice 12 11 23
Freeze Mode Time (minutes)