INSTALLATION
INSTALLING ADVANTAGE II-T C INS (CONTINUED)
Full Chimney Reline
Recommended for All Chimney Installations
Seal Chimney top with steel plate and/or pipe support
Listed Rain Cap
Horizontal Vent Through Masonry Chimney Structure
IN CANADA – Installing as a Horizon- tal Vent is NOT allowed. The fireplace chimney must be fully lined.
IMPORTANT NOTES:
Approved Liner for Factory Built (ZC) Fireplaces and
Masonry Fireplaces is 2100HT (degree F.) liner listed to UL 1777 or ULC S635. The liner must be se- curely attached to the insert flue collar and the chimney top.
Mantel
18” Min.
(457 mm) to Mantel
1” Min.
(25 mm)
to Trim
♦6” Min. Floor Protection
A flexible corrugated chimney liner has much greater resis- tance to the flow of flue gases than does a rigid liner. For this reason we recommend that a larger, 4” liner be used on ver- tical runs exceeding 15 feet or that rigid venting be used as illustrated on this page (see Full Chimney Reline).
If a flexible corrugated chimney liner is used, it must be fully extended to eliminate any sag- ging and to improve the ex- haust flow.
Mantel
Optional Posi- tive Flue
Connection18” Min. (457 mm) to Mantel
Clean
Out Tee♦ 6” Min. Floor
Protection
USA – The insert may be installed as a Hori- zontal Vent (through chimney structure) in Masonry Fireplaces if local code permits.
1” Min. (25 mm) to Trim
.
♦USA & Canada – Requires an approved noncom- bustible hearth or floor protector, 3/8” / (10 mm) millboard or equivalent (k = .84, r = 1.19) to ex- tend 6” / 150
Do not block opening at front of insert (below door).
PAGE 20