Liebert 8 Tons, 50 & 60Hz 3.14Alarm Time Delay, 3.15Common Alarm Enable, 3.16Custom Alarms

Models: 50 & 60Hz 8 Tons

1 72
Download 72 pages 64 Kb
Page 48
Image 48
3.14Alarm Time Delay

Microprocessor Control

3.14Alarm Time Delay

Each individual alarm can be programmed with a time delay (Table 13), causing the unit to delay a specified amount of time (0-255 seconds) before recognizing the alarm. The alarm condition must be present for the full amount of the time delay before the alarm will sound. If the alarm condition is diverted prematurely, the alarm will not be recognized and the time delay will automatically reset.

NOTE

For software alarms such as “loss of power” and “short cycle,” the time delay should be left at the factory default of 0.

Table 13 Alarm default time delays

 

Default Time Delay

Alarm

(seconds)

 

 

Hum Prob

2

 

 

Chng Fltr

2

 

 

Custom Alarm #1

0

 

 

Custom Alarm #2

0

 

 

Custom Alarm #3

0

 

 

High Temperature

30

 

 

Low Temperature

30

 

 

High Humidity

30

 

 

Low Humidity

30

 

 

Short Cycle 1 & 2

0

 

 

Loss of Power

0

 

 

3.15Common Alarm Enable

Each individual alarm can be selected to activate/deactivate the common alarm relay. If the energize common alarm function is set to YES, the relay is energized immediately as the alarm is enunciated, and de-energized when the alarm condition has cleared. If the alarm is completely DISABLED, the alarm has no effect on the common alarm relay. Use the UP/DOWN arrows to scroll to a particular alarm, press the ENTER button to select it, then press the ENTER key again to select Yes or No.

3.16Custom Alarms

The custom alarm messages can be selected from a list of standard alarm messages, or the operator can write his/her own message. A MAXIMUM OF THREE (3) ALARM MESSAGES CAN BE CUS-

TOMIZED.

The text for custom alarms can be changed at any time by selecting “CUSTOM ALARMS”. To change the text for a custom alarm, select the alarm you would like to change, 1, 2 or 3. Using the UP/DOWN arrows, step through the list of seven standard alarm messages (listed below) and two custom alarms. Select the alarm message desired and store it by pressing ENTER.

SMOKE DETECTED

CUSTOM 2

CUSTOM 3

STANDBY GC PUMP

WATER FLOW LOSS

STANDBY UNIT ON

CUSTOM 1

40

Page 48
Image 48
Liebert 8 Tons, 50 & 60Hz 3.14Alarm Time Delay, 3.15Common Alarm Enable, 3.16Custom Alarms, Alarm default time delays