Download 72 pages 64 Kb
Page 54
Image 54
4.4.2Humidification Operation System Activation

System Performance Microprocessor Controls

4.4Dehumidification / Humidification Percent Required

The humidity control for the MM2 is based on a calculated percent requirement for dehumidification or humidification. The percent requirement is calculated from the difference between the sensor read- ing and the humidity setpoint, divided by the sensitivity. The control method is selectable between relative and absolute. Relative humidity control is the default.

4.4.1Staged Dehumidification, Compressorized Direct Expansion (DX) Systems

For the 8-ton unit operation, 1 or 2 stage dehumidification is selected through DIP switch #7. For 2 stages, the 5-ton compressor is the lead compressor when dehumidifying. Dehumidification will be staged on at 50 and 100% call. The electric reheats are turned on at 25% cooling (reheat 1) and 25% heating (reheat 2) for improved temperature control. The reheats are deactivated at 0% and 50% cool- ing requirement, respectively. If overcooling occurs, the first stage of dehumidification is disabled at 125% call for heating. If 1 stage or 2 stage is selected, dehumidification is disabled at 200% call for heating. Dehumidification is re-enabled at 66% call for 2 stage and 33% call for 1 stage. For optional hot water heating, the valve is energized at its normal point, 100% heating requirement.

4.4.2Humidification Operation System Activation

The humidifier is activated when the humidity control calculates a requirement for 100% humidifica- tion, and is deactivated when the requirement falls below 50%.

4.4.3Dehumidification Lockout

Dehumidification is locked out if overcooling occurs. Dehumidification on the 8-ton unit is disabled at 125% (first stage) and 200% (all stages) heating requirement. Dehumidification is re-enabled at 66% and 33% heating requirement.

4.5Load Control Features

The control system monitors the compressor and prevents it from turning on within a 3-minute period of being off. If this on-off cycle occurs to often (e.g. 10 times within a one hour period) a Short Cycle Alarm will occur.

4.6Communications

The control system uses a two-wire, RS-422 channel to communicate with Liebert Site Products via a proprietary protocol. A converter board (ECA2) is available to allow communications with a “dumb” terminal or a computer using RS-232 channel. More details are provided in the Site Products and ECA2 User Manual.

The communications channel provides both monitoring and control options, including:

TEMPERATURE/HUMIDITY: Current temperature and humidity readings.

STATUS (%), Cooling/heating and humidify/dehumidify operating status.

PRESENT ALARMS: Alarms currently activated.

SETPOINTS:

Temperature Setpoint

Temperature Sensitivity

Humidity Setpoint

Humidity Sensitivity

High Temperature Alarm

Low Temperature Alarm

High Humidity Alarm

Low Humidity Alarm

ON/OFF STATUS and CONTROL

SILENCE ALARM

46

Page 54
Image 54
Liebert 8 Tons, 50 & 60Hz 4.5Load Control Features, 4.6Communications, 4.4.2Humidification Operation System Activation