Troubleshooting

8.0TROUBLESHOOTING

Table 18 Troubleshooting

Symptom

Possible Cause

Check or Remedy

 

 

 

 

No power to unit

Check voltage at input terminal block.

 

 

 

 

Control voltage fuses (at

Locate and repair short. Replace fuses.

 

transformer) open

 

 

Unit will not start

Float switch relay has closed

Check drain and line. Access through left panel. Power must be

due to high water in the

cycled at the disconnect to reset. Check return air static pressure is

 

condensate pan.

less than 0.3" wg.

 

 

Check terminal 37 and 38 for jumper or N/C contact. Check pins P39-

 

Jumper not in place

1 and P39-2 for jumper, or N/C firestat contact. Check pins P40-12

 

 

and 1HWAR-Com for jumper or N/C smoke detector contact.

 

“Cooling” is not displayed at

Adjust TEMP control setpoint and sensitivity to require cooling.

 

the control panel.

 

 

 

Short cycle prevention

Control software delays compressor 3 minutes cooling, from stop to

 

control.

start

 

Compressor contactor not

Check for 24 VAC ± 2 VAC at terminals TB2 to TB1 for Compressor 1;

 

TB6 to TB5 for Compressor 2. If voltage, check contactor. If voltage,

No cooling

pulling in.

check freeze stat (FR1 and FR2).

 

 

 

 

Compressor high head

See below for cause.

 

pressure.

 

 

 

Plugged filter/dryer.

Replace filter/dryer.

 

 

 

 

Low refrigerant charge.

Check pressure gauges. At low ambient temperatures, proper

 

refrigerant charge is very important on units with Lee-Temp receivers.

 

 

 

Insufficient air flow across

Remove debris from coil and air inlets.

 

condenser coil

 

 

Compressor high

Water/Glycol-Cooled only:

 

head pressure

No fluid flowing through

Check fluid supply to regulating valve. Adjust valve if necessary.

 

condenser.

 

 

Condenser fan not operating

Check fan operation.

 

 

 

 

DIP switch not set to enable

See DIP switch settings Table 17.

 

humidifier option

 

 

 

“HUMIDIFY” not displayed

Increase humidity control setpoint and sensitivity to require

 

at control panel

humidification.

 

 

Check voltage at 35-1 and 35-5 on interface board for 24 VAC ±2

 

Defective board

VAC. If no voltage, check wiring and/or replace board. Check wiring

 

 

from control panel to board.

Humidifier does

 

 

 

Humidity display will indicate dashes. Check wiring from temperature/

not operate

Failed humidity sensor

humidity board to the control board and from the wall box to the

 

control board. Replace wallbox or temperature/humidity circuit board

 

 

 

 

(if remote).

 

 

 

 

No water flow

Make sure switch is in Run position. Check humidifier water supply

 

(including filter screen) and check nylon overflow line if canister is full.

 

 

 

Canister fill rate is not

Check fill valve screen opening and capillary tube for obstructions.

 

keeping up with the steam

 

Check water supply pressure (minimum 10 psig).

 

output

 

 

 

 

 

 

DIP switch not set to enable

See DIP switch settings Table 17.

 

reheat option

 

 

 

“HEAT” not displayed at the

Increase temperature setpoint to require heating.

Reheat will not

control panel

 

operate

 

 

Reheat safety open,

Check voltage at P34-4 or P34-6 to P34-10 on interface board for 24

 

defective reheat contact or

VAC ± 2 VAC. If voltage, check reheat contactor and reheat safety. If

 

defective board

no voltage, check wiring and/or replace board.

 

Element is burned out

Turn off power. Check element continuity with Ohm meter.

 

 

 

58

Page 66
Image 66
Liebert 8 Tons, 50 & 60Hz user manual Troubleshooting