Microprocessor Control

3.18Run Diagnostics

By selecting Run Diagnostics, maintenance personnel can check system inputs, outputs, and conduct a test of the microcontroller circuit board from the wall box control. A review of the system inputs and the microcontroller test can be done without interrupting normal operation.

Test Outputs

• When this feature is selected, the controller is effectively turned off. When stepping from one load to the next, the previous load is automatically turned off. The loads can also be toggled on/off by selecting “ENTER”. Once turned on, the output will remain on for five minutes unless toggled off or the test outputs function is exited by selecting “MENU/ESC” (Compressor is limited to 15 sec- onds on to prevent damage.

! CAUTION

Testing compressor output for more than a few seconds could damage the compressor. To eliminate damaging the compressor during testing, DO NOT test compressor output for more than a few seconds.

! CAUTION

Extended unit operation in the test outputs mode for troubleshooting may cause damage to unit. DO NOT operate unit in the test outputs mode any longer than is necessary for troubleshooting.

NOTE

Fan turned on with all loads.

The outputs are:

Main Fan

Compr1 (3-ton)

Compr1 & HGBP1

Compr2

Compr2 & HGBP2

Compr1 & Compr2

Chill Water/Gly (if present)

Reheat 1

Reheat 2

SCR Reheats (if present)

Humidifier

Common Alarm

Test Inputs

With the unit on and the fan running, the input states may be displayed for the following devices:

Input Power

High Water in Pan

High Head Comp1

High Head Comp2

Air Sail Switch (requires additional factory-installed components)

Filter Clog

Humidifier Prob.

Custom Alarm #1

Custom Alarm #2

Custom Alarm #3

42

Page 50
Image 50
Liebert 8 Tons, 50 & 60Hz user manual Run Diagnostics, Test Outputs, Test Inputs