Liebert 50 & 60Hz, 8 Tons 2.7.1Location Considerations, 2.7.2Piping Connections, Regulating Valve

Models: 50 & 60Hz 8 Tons

1 72
Download 72 pages 64 Kb
Page 35
Image 35
2.7.1Location Considerations

Site Preparation and Installation

2.7Indoor Water- and Glycol-Cooled Condensing Unit Installation

2.7.1Location Considerations

The condensing unit may be located above the dropped ceiling or any remote indoor area. If noise is of concern, the condensing unit should be located away from personnel. Normal operating sound may be objectionable if the condensing unit is placed near quiet work areas.

To mount the unit in the ceiling, refer to 2.4 - Installing the Evaporator or Chilled-Water Units.

2.7.2Piping Connections

Details for Refrigerant (R-22) Loop piping are in 2.4.3 - Piping Connections and Coolant Requirements.

Water/Glycol Piping Considerations

Refer to Figure 20 for recommended field installed piping hardware such as shut-off valves and hose- bibs. Water filters should be installed if water quality is poor. Filters will extend the service life and efficiency of the condensers.

Condensing Unit Fluid Requirements

The maximum fluid pressure is 150 psi standard pressure or 350 psi for high pressure units (Refer to unit serial tag and model number description page at beginning of this manual).

NOTE

HVAC grade ethylene or propylene glycol should be used on glycol systems.

Automotive antifreeze must not be used.

Regulating Valve

Water/Glycol-cooled units include a coolant flow regulating valve which is factory adjusted and should not need field adjustment.

Standard water pressure and high water pressure valves are adjusted differently. Contact Liebert Service before making any adjustments.

2.7.3Electrical Connections

Refer to 2.4.4 - Electrical Connections, Evaporator or Chilled-Water Unit for general wiring requirements and cautions. Refer to electrical schematic when making connections. Refer to serial tag for full load amp and wire size amp ratings.

Control Connections

A six-wire control connection is required from the evaporator unit to the water/glycol condensing unit. Two (2) additional wires are required when hot gas bypass is ordered. Glycol-cooled units also require a two-wire control connection to the drycooler and pump package.

27

Page 35
Image 35
Liebert 50 & 60Hz, 8 Tons 2.7.1Location Considerations, 2.7.2Piping Connections, Water/Glycol Piping Considerations