Image 67
Table 18 Troubleshooting (continued)

Troubleshooting

Table 18 Troubleshooting (continued)

Symptom

Possible Cause

Check or Remedy

 

 

 

Cooling cycle too

Sensor response delay too

Increase sensor response delay. See 3.12 - Calibrate Sensors.

short

short

 

Display freezes

 

During period of low humidity, static electricity can cause the control

 

program to freeze or display incorrect information. Although this is

and control pads

Static discharge

unlikely, the control can be reset by cycling power from the disconnect

do not respond

 

 

switch.

 

 

 

 

 

Condensate

Open or short circuit in

Find open or short circuit and repair power to pump.

pump does not

wiring

operate

 

 

 

 

 

 

 

 

Temperature display will indicate dashes. Check wiring from

Continuous

Failed temperature sensor

temperature/humidity board (remote sensors) to the control board or

Cooling

from control board to wallbox. Replace temperature/humidity circuit

 

 

 

board (remote sensors) or wallbox.

 

 

 

Continuous

 

 

Heating

Shorted wiring or failed

Check wiring and/or replace control board.

Dehumidification

control board

 