Liebert 50 & 60Hz, 8 Tons Footprint Dimensions, DPN000131 Rev0, Site Preparation and Installation

Models: 50 & 60Hz 8 Tons

1 72
Download 72 pages 64 Kb
Page 33
Image 33
FOOTPRINT DIMENSIONS

Site Preparation and Installation

Figure 16 Footprint dimensions - outdoor condensing unit

GUARD

 

HEIGHT

TOP

 

AIR

D

DISCHARGE

RIGHT

 

 

AIR

 

INTAKE

B

 

LEFT

SHADED AREA

AIR

INDICATES A RECOMMENDED

INTAKE

CLEARANCE OF 18" (457mm)

 

 

FOR PROPER AIR FLOW

2

"

(51mm)

 

A

 

 

C

 

SHADED AREA

 

 

 

SHADED AREA

INDICATES A RECOMMENDED

 

 

REMOVABLE FRONT PANEL FOR

INDICATES A RECOMMENDED

CLEARANCE OF 18" (457mm)

CLEARANCE OF 24" (610mm)

FOR PROPER AIR FLOW

 

ACCESS TO HIGH VOLTAGE &

 

FOR COMPONENT

 

 

LOW VOLTAGE CONNECTIONS

 

 

ACCESS AND REMOVAL

 

 

AND REFRIGERATION COMPONENTS

 

 

 

 

 

36 1/8 "

 

4 " TYP.

 

 

 

(918mm)

 

53 3/16 "

 

 

 

 

(102mm)

(1351mm)

 

 

 

 

2 " TYP.

 

1/2" Bolt-Down Holes

 

 

 

(51mm)

 

(6 places)

 

 

 

 

 

4 23/32 "

 

 

 

 

2 "

(120mm)

 

 

 

 

 

 

 

 

 

(51mm)

 

25 3/32 "

 

 

 

32 1/8 "

 

 

 

 

(816mm)

 

(637mm)

 

 

2 "

 

 

 

 

 

46 7/32 "

(51mm)

 

 

 

 

 

 

(1174mm)

 

 

 

 

 

FOOTPRINT DIMENSIONS

DPN000131_Rev0

Model

Dimensional Data in. (mm)

Net Weight

 

 

 

 

 

60 Hz

50 Hz

Width (A)

Height (B)

Depth (C)

lbs (kg)

PFC096A-_L

PFC095A-_L

53 (1343)

36-1/4 (918)

38-1/2 (978)

488 (222)

PFH096A-_H

PFH095A-_L

53 (1343)

36-1/4 (918)

38-1/2 (978)

488 (222)

25

Page 33
Image 33
Liebert 50 & 60Hz, 8 Tons user manual Footprint Dimensions, DPN000131 Rev0, Site Preparation and Installation