Liebert 50 & 60Hz, 8 Tons user manual 3.17Custom Text, LCD Display Contrast, Nonvolatile Memory

Models: 50 & 60Hz 8 Tons

1 72
Download 72 pages 64 Kb
Page 49
Image 49
3.17Custom Text

Microprocessor Control

3.17Custom Text

To modify the two custom alarm messages select “CUSTOM TEXT”. Then select “Custom Text #1,” “Custom Text #2” or “Custom Text #3.” Text can be up to 16 characters in length and can be either a blank space or any of the following alphanumeric characters and symbols:

A,B,C,D,E,F,G,H,I,J,K,L,M,N,O,P,Q,R,S,T,U,V,W,X,Y,Z

#,%,*,-

0,1,2,3,4,5,6,7,8 or 9

Use the UP/DOWN arrows to select a character, then press ENTER. The cursor will move to the next space where you may once use the UP/DOWN arrows to select another character, etc. The cus- tom text alarm will be displayed only if the alarm is selected in Custom Alarms.

LCD Display Contrast

The level of contrast due to the viewing angle of the LCD display can be adjusted using a potentiome- ter screw, inside the wall box next to the display.

Nonvolatile Memory

All critical information is stored in nonvolatile memory. Setpoints and setup parameters are kept inside the microcontroller in EEPROM.

Equipment Options Switches

Equipment options are selected and enabled using DIP switches 1 through 7. These are located on the control board near TB3. These switches are factory set and should not require any user changes. The setting and function of the switches can be individually read on the LCD display.

NOTE

In order to update the DIP switch settings, power must be cycled off, then on, from the unit disconnect switch.

Table 14 Equipment switch settings (unit control board)

Switch

OFF Position

ON Position

 

 

 

1

Step Cool

Ramp Cool

 

 

 

2

Step Heat

Ramp Heat

 

 

 

3

Not Used

Not Used

 

 

 

4

No GLYCOOL

GLYCOOL

 

 

 

5

Disable 1 stage CW

Enable 1 stage CW

 

 

 

6

Not used

Not used

 

 

 

7

1-stage

2-stage

 

dehumidification

dehumidification

8

Disable SCR Reheat

Enable SCR Reheat

 

 

 

Table 15 Switch settings (wallbox board)

Switch

OFF Position

ON Position

 

 

 

1

Beeper Disable

Beeper Enable

 

 

 

2

Not Used

Not Used

 

 

 

3

Not Used

Not Used

 

 

 

4

Enable Reheat

Disable Reheat

 

 

 

5

Enable Hum.

Disable Hum.

 

 

 

6

Enable Dehum.

Disable Dehum.

 

 

 

7

Disable Setback

Enable Setback

 

 

 

8

Enable Password

Disable Password

 

 

 

41

Page 49
Image 49
Liebert 50 & 60Hz, 8 Tons user manual 3.17Custom Text, LCD Display Contrast, Nonvolatile Memory, Equipment Options Switches