Liebert 50 & 60Hz, 8 Tons 6.2.1Electric Panel, 6.2.2Filters, 6.2.3Blower System, Air Distribution

Models: 50 & 60Hz 8 Tons

1 72
Download 72 pages 64 Kb
Page 59
Image 59
6.2.1Electric Panel

System Operation, Testing, and Maintenance

6.2Maintenance and Component Operation

6.2.1Electric Panel

The electric panel should be inspected on a semi-annual basis for any loose electrical connections.

6.2.2Filters

Filters are usually the most neglected item in an environmental control system. In order to maintain efficient operation, they should be checked monthly and changed as required. ALWAYS TURN POWER OFF BEFORE REPLACING FILTERS.

Filters are replaced by opening the hinged door on the return air filter box.

6.2.3Blower System

Monthly inspection of the blower package includes: motor mounts, belts, fan bearings, and impellers.

Fan impellers should be thoroughly inspected and any debris removed. Check to see if they are tightly mounted on the fan shaft and do not rub against the fan housing during rotation. Motor and fan bear- ings are permanently sealed and self-lubricating and do NOT need lubricated.

The drive belt should be checked monthly for signs of wear and proper tension. Pressing on belts mid- way between the sheave and pulley should produce from 1/2" to 1" (12 to 25 mm) of deflection. Belts that are too tight can cause excessive bearing wear.

Belt tension can be adjusted by raising or lowering the fan motor base. Loosen nut above motor mounting plate to remove belt. Turn nut below motor mounting plate to adjust belt tension. If belt appears cracked or worn, it should be replaced with a matched belt (identically sized). With proper care, a belt should last several years.

NOTE

After adjusting or changing the belt, always be certain that motor base nuts are tightened. The bottom adjustment nut should be finger tight. The top locking nut should be tightened with a wrench.

Air Distribution

Since all unit models are designed for constant volume air delivery, any unusual restrictions within the air circuit must be avoided. High efficiency filters can reduce air performance and evaporator capacity.

Blower Removal (Evaporator)

If the blower or bearings must be removed or serviced, use the following procedure.

1.Prepare the main center section of the three (3) piece electric panel by first marking and disconnecting all power and control wiring entering the panel.

2.Remove the electric panel by removing screws from top and bottom sections

3.Remove the bottom electric panel mounting flange from unit base.

4.Remove the belt, motor, motor mounting plate, and tensioning bolt.

5.Remove the four (4) screws holding the blower mounting rails to the sled.

! CAUTION

Protect refrigerant and water piping from damage.

6.Remove the (4) screws holding the blower mounting rails to the sled.

7.Slide the blower/rail assembly forward and rotate approximately 45 degrees and remove from unit.

8.Replace failed parts.

51

Page 59
Image 59
Liebert 50 & 60Hz 6.2.1Electric Panel, 6.2.2Filters, 6.2.3Blower System, Air Distribution, Blower Removal Evaporator