Installation and User Manual
1.5System Specifications1.5.1Electrical Characteristics
| UPS power rating in kVA |
|
|
| 100 |
| 130 | 150 | 180 | 200 | 225 |
| |||
| Normal AC input |
|
|
|
|
|
|
|
|
|
|
| |||
| number of conductors |
| 3 phases |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||||
| rated voltage and tolerances |
| 480 V ± 10% (adjustable to ± 15%) |
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| rated frequency and tolerances |
| 60 Hz / ± 10% |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| THDI |
|
|
|
|
| < 14% |
| < 11% | < 10% | < 8% | < 7.6% | < 7.5% |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| power factor |
|
|
| up to 0.9 |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Bypass AC input |
|
|
|
|
|
|
|
|
|
|
| |||
| number of conductors |
| 3 phases | 3 phases + neutral |
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| rated voltage and tolerances |
| 480 V / ± 10% |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| rated frequency and tolerances |
| 60 Hz / ± 10% |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Load |
|
|
|
|
|
|
|
|
|
|
|
|
| |
| number of conductors |
| 3 phases | 3 phases + neutral |
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Ph/Ph voltages |
|
|
| 480 V |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Ph/N voltages |
|
|
| 277 V |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| voltage fluctuations (Ph/Ph,Ph/N) |
| ± 1% |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| adjustable frequency and tolerances |
|
|
|
|
|
|
|
|
|
| ||||
| (on battery power) |
| 60 Hz ± 0.05 Hz |
|
|
|
|
|
| ||||||
| synchronization with bypass |
| ± 0.5 Hz (adjustable from ± 0.25 Hz to ± 2 Hz) |
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
| ||||||
| transient voltage variation for 0 to 100% load step change | ± 2% (with battery), |
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |||||
| permissible overloads |
| 150% for 1 minute, 125% for 10 minutes |
|
|
|
|
| |||||||
| Isc Ph/Ph (% of I rated) |
|
|
| 4.7 |
| 3.6 | 3.2 | 2.6 | 2.4 | 2.1 |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Isc Ph/N (% of I rated) |
|
|
| 7.4 |
| 5.7 | 5 | 4.1 | 3.7 | 3.3 |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| THDU Ph/Ph and Ph/N for linear load | < 1.5% Ph/Ph, < 2% Ph/N |
|
|
|
|
|
|
|
| |||||
| THDU Ph/Ph and Ph/N for | < 2% Ph/Ph, < 3% Ph/N |
|
|
|
|
|
| |||||||
| (at 80% of Pn) |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Battery |
|
|
|
|
|
|
|
|
|
|
|
|
| |
| voltage floating |
|
|
| 512V to 561V |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |||||
| standard battery type |
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| UPS characteristics |
|
|
|
|
|
|
|
|
|
|
| |||
| active power (kW) |
|
|
| 100 |
| 130 | 150 | 180 | 200 | 202.5* |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| efficiency at 50% load (%) |
|
|
| 90.5 |
| 91 | 92 | 92.5 | 92.5 | 93 |
| |||
| (values ± 1%) |
|
|
|
|
|
|
|
|
|
|
|
|
| |
| efficiency at 100% load (%) |
|
|
| 92.5 |
| 93 | 93 | 93 | 93.5 | 93.5 |
| |||
| (values ± 1%) |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| heat losses (1) |
|
| in KW |
|
| 8.1 |
| 9.8 | 11.3 | 13.5 | 13.9 | 14.1 |
| |
|
|
|
|
| in cal./s |
|
| 1940 |
| 2350 | 2700 | 3240 | 3340 | 3380 |
|
|
|
|
|
|
|
|
|
|
|
| |||||
| storage temperature range ºF (ºC) |
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||||||||
| operating temperature range ºF (ºC) | 32 to 95, 104 for 8 hours (0 to 35, 40 for 8 hours) |
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| |||||
| relative humidity |
|
|
| 95% maximum non condensing at ambient temperature |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||
| maximum operating altitude without derating, FT(m) | < 3280 (< 1000) |
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| noise level (dBA) |
|
|
| 62 |
| 63 | 64 | 65 | 67 | 68 |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| dimensions, in. (mm) | width | 47.8 (1215) |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| depth | 33 (840) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| height | 74.8 ± .39 (1900 ± 10) |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| weight lbs (kg) |
|
|
| 3050 (1388) |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
| ||||
| standards | design |
| NFPA / NEC / NEMA / OSMA |
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| product and safety | UL 1778 - ULC |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |||||||
|
|
| electromagnetic compatibility | FCC Part 15, Subport J, Class A - IEEE587 / ANSI 62.41 |
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
(1): The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system. * pf of 225kVA unit has 0.9 and remaining units have 1.0.
Introduction | 1 — 5 |