Installation and User Manual

1.5System Specifications1.5.1Electrical Characteristics

 

UPS power rating in kVA

 

 

 

100

 

130

150

180

200

225

 

 

Normal AC input

 

 

 

 

 

 

 

 

 

 

 

 

number of conductors

 

3 phases

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rated voltage and tolerances

 

480 V ± 10% (adjustable to ± 15%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rated frequency and tolerances

 

60 Hz / ± 10%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THDI

 

 

 

 

 

< 14%

 

< 11%

< 10%

< 8%

< 7.6%

< 7.5%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power factor

 

 

 

up to 0.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bypass AC input

 

 

 

 

 

 

 

 

 

 

 

 

number of conductors

 

3 phases

3 phases + neutral

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rated voltage and tolerances

 

480 V / ± 10%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rated frequency and tolerances

 

60 Hz / ± 10%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

number of conductors

 

3 phases

3 phases + neutral

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ph/Ph voltages

 

 

 

480 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ph/N voltages

 

 

 

277 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage fluctuations (Ph/Ph,Ph/N)

 

± 1%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

adjustable frequency and tolerances

 

 

 

 

 

 

 

 

 

 

 

(on battery power)

 

60 Hz ± 0.05 Hz

 

 

 

 

 

 

 

synchronization with bypass

 

± 0.5 Hz (adjustable from ± 0.25 Hz to ± 2 Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transient voltage variation for 0 to 100% load step change

± 2% (with battery), +2%/-6% (without battery)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

permissible overloads

 

150% for 1 minute, 125% for 10 minutes

 

 

 

 

 

 

Isc Ph/Ph (% of I rated)

 

 

 

4.7

 

3.6

3.2

2.6

2.4

2.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Isc Ph/N (% of I rated)

 

 

 

7.4

 

5.7

5

4.1

3.7

3.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THDU Ph/Ph and Ph/N for linear load

< 1.5% Ph/Ph, < 2% Ph/N

 

 

 

 

 

 

 

 

 

THDU Ph/Ph and Ph/N for non-linear load

< 2% Ph/Ph, < 3% Ph/N

 

 

 

 

 

 

 

(at 80% of Pn)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage floating

 

 

 

512V to 561V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

standard battery type

 

gas-recombination sealed lead-acid battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS characteristics

 

 

 

 

 

 

 

 

 

 

 

 

active power (kW)

 

 

 

100

 

130

150

180

200

202.5*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

efficiency at 50% load (%)

 

 

 

90.5

 

91

92

92.5

92.5

93

 

 

(values ± 1%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

efficiency at 100% load (%)

 

 

 

92.5

 

93

93

93

93.5

93.5

 

 

(values ± 1%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heat losses (1)

 

 

in KW

 

 

8.1

 

9.8

11.3

13.5

13.9

14.1

 

 

 

 

 

 

in cal./s

 

 

1940

 

2350

2700

3240

3340

3380

 

 

 

 

 

 

 

 

 

 

 

 

 

storage temperature range ºF (ºC)

-13 to 158 (-25 to 70) dry heat — unit without battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-4 to 113 (-20 to 45) — unit with battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operating temperature range ºF (ºC)

32 to 95, 104 for 8 hours (0 to 35, 40 for 8 hours)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

relative humidity

 

 

 

95% maximum non condensing at ambient temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

maximum operating altitude without derating, FT(m)

< 3280 (< 1000)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

noise level (dBA)

 

 

 

62

 

63

64

65

67

68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

dimensions, in. (mm)

width

47.8 (1215)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

depth

33 (840)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

height

74.8 ± .39 (1900 ± 10)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

weight lbs (kg)

 

 

 

3050 (1388)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

standards

design

 

NFPA / NEC / NEMA / OSMA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

product and safety

UL 1778 - ULC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

electromagnetic compatibility

FCC Part 15, Subport J, Class A - IEEE587 / ANSI 62.41

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1): The losses indicated are those produced at full rated load with the battery float charging. They must be taken into account when sizing the ventilation system. * pf of 225kVA unit has 0.9 and remaining units have 1.0.

86-133060-00 A00

Introduction

1 — 5