Manuals
/
Brands
/
Computer Equipment
/
Power Supply
/
MGE UPS Systems
/
Computer Equipment
/
Power Supply
MGE UPS Systems
225KVA manual
78
1
78
104
104
Download
104 pages, 1.2 Mb
Galaxy PW
™
UPS 100 to 225kVA
(This page left blank intentionally)
5 — 8
86-133060-00
A00
Contents
w w w . m g e u p s . c o m
Features
Installation and User Manual
Galaxy PW™ UPS 100 to 225kVA
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
WARNING
Opening enclosures expose hazardous voltages. Always refer service to
Installation and User Manual
controlled indoor area free of conductive contaminants
This equipment is intended only for installations in a RESTRICTED ACCESS
LOCATION
Ce matériel est destiné seulement pour des installations dans un EMPLACE
CAUTION: Record All Serial Numbers
Galaxy PW™
Page
Contents
(continued)
Operation (continued)
Operation with Engine Generator Set
Inverter Shutdown or Overload
Parallel UPS With Redundancy
Output Voltage Quality and Continuity
Appendices
Appendix A
Appendix B
Appendix C
MGE Warranty & Proprietary Rights for Three Phase Products
Figures
Handling Cabinet From the Bottom or Rolling on Bars
Dismantling Leg Supports and Attaching Spacers to Cabinet. . . . . . . . .2 —
Component Layout in a Battery Cabinet or a
Parallel UPS Unit for Increased Output
Figures (continued)
Introduction
1.2General Description
The other power cables for connections between cabinets are not supplied
1.3System Major Power Components
Rectifier/charger module (A)
Battery unit (D)
Inverter module (B)
Static bypass module (C)
1.4Different Types of Galaxy PW™ Systems
1.4.1Single UPS System
Legend:
QF1
Q5N
1.5System Specifications
1.5.1Electrical Characteristics
1.6Electrical Parameters for Selecting Protective Devices
1.6.1Normal AC Source
It is essential to choose the type of circuit breaker according to its breaking
capacity and the prospective short-circuitcurrent at its place of installation
This choice must also be made so as to protect the static-switchsemicon
1.6.2Bypass AC Source
inrush current caused by magnetization of the transformer windings
Electrical parameters for bypass AC source (480 V)
UPS output
maximum permissible current
1.7Recommended Protection
1.7.1Protection Upstream of Galaxy PW™
Ratings
rated UPS
CB on normal
1.8Parallel Connected UPS Units
Parameters
rated unit
number of
total UPS
Page
System Setup
2.1Receiving
2.1.1Handling
Rolling on Bars (B)
From the Bottom (A)
Fork tunnel height:
From Bottom
On Rollers
2.1.2Storage
Transport: the temperatures must remain within the -30°to +50°C range and the
duration should not exceed 30 days
2.2Unpacking
2.3Galaxy PW™ Cabinet Major Components
M N
O P
1, 2, E,F
2.4Battery Cabinet
AA:
2.5Remote External Maintenance Bypass Cabinet
350A and 1200A
350A
1200A
2.6General Instructions for Screens
2.6.1Control Panel Indicators and Definitions
Control Panel Alphanumeric Legend:
"Rectifier/charger" light
"Battery light
"Static-bypass
light
2.7System Start-up
2.7.1Single UPS unit or Redundant Parallel UPS
2.8Parallel UPS Unit for Increased Output
external bypass
Page
Installation
3.3Power-CircuitWiring Diagrams
3.4Hot Swap Options
Page
3.5Connections Between Cabinets
3.5.1Connections Between UPOZ Boards
(A)
'UPOZ' Galaxy PWTM
XM137
XM138
Page
Page
Page
Page
Page
Page
Mounting Hole
board
Cable Entry
Dimensions: 75 x 75 x 21 mm
each
signal
Media Contacts 11 Remote Indicators Board
XR2 XR3 XR4 XR5
NOTE: the corresponding IBM AS400 signal names
are given in parapharase
XR2
Operation
4.1.3Single UPS Unit
4.1.4Parallel UPS Unit
4.2Operation in On-lineMode
4.2.1Normal Operation
(B)
In parallel Galaxy PW™ systems, the power drawn by the load is equally shared
between the different units
4.2.2Operation with the Normal AC Source Down
(D)
4.3Operation with the Normal AC Source Restored
step 2:
seconds) (parameter defined by after-salessupport department), the charger
automatically supplies the floating voltage given the low battery discharge
U/I
U charge/floating
U "floating
current
current
constant voltage
4.5Battery Time
The "low battery shutdown" warning signal can be sent with an adjustable time
delay prior to the effective end of battery power
4.6Inverter Shutdown or Overload
A B
4.6.1Single UPS Unit (On-linemode)
Transfer conditions are not satisfied when bypass AC source characteristics are
outside tolerances (voltage: ±10%. frequency as per personalization. phase sync
with inverter ±3°)
4.6.2Parallel UPS Without Redundancy
4.6.3Parallel UPS With Redundancy
4.7Output Voltage Quality and Continuity
4.7.1Steady State Voltage Regulation
4.7.2Transient Voltage Regulation
4.8Measurement System
Normal AC source
Inverter output
Total load
Bypass AC source
RMS
LOAD
CHOOSE LANGUAGE
DATE AND TIME
CONTRAST SETUP
INVERSE VIDEO
BUZZER SETUP
DATE AND TIME SETUP
YEAR
MONTH
DAY
HOURS
BATTERY TEST RESULT OK
BATTERY TEST RESULT NOT OK
TIME SINCE LAST TEST
WEEK --DAY --HOUR
LAST BATTERY TEST RESULT OK
(ALARM MESSAGE N° 1)
(ALARM MESSAGE N° 2)
(LAST ALARM MESSAGE)
02/09/1997 07:25:03 Appearance:
MAINS 2 INPUT SWITCH Q4S IS OPEN
03/09/1997 15:30:23 Disappearance:
OVERLOAD
RATED CURRENT PER PHASE = _ _ _ A
DATE AND
TIME SETUP
>YEAR
MONTH
DAY
FIGURES
SINCE
COMMISSIONING
total backup
time (h):
FIGURES SINCE RESET
nb of
backups:
backups
min:
PARAMETER NAME (units)
T=30 days
▼last read: 05/09/1997
BATTERY
CAPACITY (Ah)
days
▼ last read: 05/09/1997
BACKUP (min)
Maintenance
5.2Replacement Parts
Level Description
5.2Maintenance Isolation Procedures
5.2.1Single UPS Unit
UPS Isolation
Page
Galaxy PW
external bypass
5.4Battery Maintenance
◗Sealed lead-acidBatteries:
◗Vented lead-acidBatteries:
5.5Visual Check
In redundant parallel UPS systems the check may be carried out successively on
0080C8ABAA01
5.8.2Two-channelNetwork Board
Page
Appendices
Appendix A
Key ø
"Anomaly" indicator light
Key ⁄
18"Battery" Key ı
19"Forced-transfer
Display of Primary and Secondary Messages
Most functions may be directly accessed. For example, when voltagemeasure
ments are currently displayed, it is possible to directly access current
measurements by pressing the "A" button
Select English U. S. as the display language to match the displays as presented
LOAD PROTECTED
ON-LINEMODE
PARALLEL ON-LINEMODE
LOAD NOT PROTECTED
ON-LINEMODE Ø
ECO MODE
ECO MODE Ø
LOAD FORCED TO INVERTER
LOAD ON MAINS
MAINS 2 OUTSIDE TOLERANCES
INTERNAL UPS FAULT
LOAD TRANSFER FAULT
CALL MAINTENANCE
OVERLOAD
RATED CURRENT PER PHASE = XXXA
BATTERY
CHARGING
BAT.=XXX A
U BAT. = XXX
The battery is currently be recharged
THE NUMBER OF UPS READY IS INSUFFICIENT
LOAD TRANSFER IN STANDBY
INVERTER NOT CONNECTED
PARALLEL UPS
FORCED TRANSFER INHIBITED
Page
Appendix B
Page
Appendix C
Galaxy PWTM UPS 100 to 225 kVA
MGE Warranty & Proprietary Rights for Three Phase Products
MGE Warranty
Proprietary Rights Statement
Page
MGE Customer Care Center
Technical Support and Product Services
Who To Contact
Technical Support:
1-800-523-0142 (during business hours)
Page
Glossary
Page
Page
Page
Reorder Form
1660 Scenic Avenue
Costa Mesa, CA
Page
Page
Contact MGE
United States
MGE UPS SYSTEMS
1660 Scenic Ave
Costa Mesa, CA