Galaxy PW™ UPS 100 to 225kVA
3.8.2Connection of the Battery "Temperature Monitor"
This unit must be connected to the XR2 connector on the remote indications "Media Contacts 11" board of the UPS cabinets. For the location of the "Media Contacts 11" board, marked "O" see Figure
Use a shielded cable made up of 2 twisted telephone pairs with a conductor
In the case of a parallel UPS configuration, the connections between cabinets may be made by means of a shielded cable made up of 1 or 2 twisted telephone pairs. In this case, the total length of all the connecting cables must not exceed 100 m;
A "Temperature Monitor" unit can be connected to several UPS cabinets only when the batteries of these cabinets are located in the same room at the same ambient temperature.
Figure
Battery Temperature Monitor |
| Shielded cable | ||
|
|
|
| (2 twisted |
|
|
|
| telephone pairs) |
DC + |
|
|
| DC- |
|
|
|



XR2 connector on 'Media Contacts 11' Board:
12 |
|
|
| each |
|
|
| ||
11 |
|
|
|
|
10 |
|
|
|
|
9 |
|
|
|
|
8 |
|
|
|
|
7 |
|
| ||
6 | power supply | |||
5 | +12V |
|
| |
4 |
| DC + | temperature | |
3 |
| DC - | ||
| signal | |||
2 |
|
| ||
|
|
|
| |
1 |
|
|
|
|
Refer to Appendix C for
3 — 12 | Installation |