Galaxy PWUPS 100 to 225kVA

CAUTION

Work should be carried out in accordance with applicable safety regulations. to

 

avoid interrupting the load, the various switching operations must be carried out

 

in the correct order. Operations are explained in diagrams placed next to the

 

switches. the system cabinet is only partially powered down. The load is still

 

supplied via the bypass AC source and switch Q3BP.

 

 

5.3Steps for Parallel UPS Redundancy to Increase Output

CAUTION

PARALLEL UPS WITH EXTERNAL MAINTENANCE BYPASS During mainte-

 

nance operation, when CB1 (MBP) is closed and CB2 (UPS ISOLATION) is

 

open, each UPS control panel display will show a message “LOAD

 

PROTECTED” when the UPS is placed in ON-LINE MODE. In this mode the

 

critical load is not protected because it is supplied by the maintenance

 

bypass power.

 

 

First Isolate all UPSs: (Refer to section 5.2, page 5—2)

See Figure 5-6.

Proceed in the following order: (See Figure 5-4)

1.Shut down the inverters (press the "inverter OFF" buttons 8 for three seconds).

2.Close switch Q3BP and open switch Q5N in the external bypass unit.

3.Open switches Q1, QF1, and Q5N on the UPS units.

Figure 5-4: Isolate All UPS’s Procedures Diagram.

78

 

Galaxy PW

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

2

3

4

 

 

 

 

 

 

external bypass

 

 

 

Q1

Q4S

Q5N

Q3BP

0

1

0

1

 

 

 

4

1

 

1

 

1

 

 

1

 

1

0

0

0

Q5N

0

0

 

 

 

 

 

 

 

QF1

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

0

I

 

 

 

 

 

 

 

1

 

1

 

1

 

 

 

 

 

6

0

0

0

 

 

 

 

 

 

 

 

 

 

 

 

5 — 4

Maintenance

86-133060-00 A00