Galaxy PW™ UPS 100 to 225kVA
-normal AC source outage or voltage drop.
-rectifier/charger shutdown.
-rectifier/charger current limiting.
This signal, which may be used to initiate process saving and shutdown procedures, is
-maintenance bypass switch Q3BP is closed,
-bypass AC source input switch Q4S is open,
-inverter output switch Q5N is open,
-battery circuit breaker QF1 is open.
In the event the "emergency off" button is pressed or to avoid an excessive battery discharge (lasting more than three times the rated backup time plus two hours).
Repo Contact: |
| ||
|
| emergency shutdown. | |
"General Alarm" information: | |||
|
| - internal faults. | |
|
| - information on temperatures outside tolerances in the battery room (optional). | |
|
| - overload information (> In). | |
|
| - | |
|
|
| |
NOTE | The maximum breaking capacity of the changeover contacts is 5A at 250V. | ||
|
|
|
|
3 — 8 | Installation |