Installation and User Manual

3.7"Media Contacts 11" Standard Auxiliary Circuits Connection

Connecting the auxiliary circuits to the three connectors on the "Media Contacts 11" board in the Galaxy PW™ UPS cabinet, see the position of this board, marked "O", see Figure 2-3, page 2—5.

Recommended cable cross-section: 1 mm2. The male connectors that fit the female connectors on the board (XR2

to XR5) are supplied. The contacts are volt-free and are shown in the diagram under the following conditions: UPS

on, contact at rest. Contact breaking capacity: 250 V, 5 A.

Figure 3-8: Standard Auxiliary Circuits Connections.

Media Contacts 11 Board

12 - - - - - - - - - -1 10 - - - - - - - -1 10 - - - - - - - -1 10 - - - - - - - -1

XR2 XR3 XR4 XR5

XR2

XR3

XR4

XR5

1 - - - - - - - - -10 1 - - - - - - - - -10 1 - - - - - - - - -10 1- - - - - - - - - - 12

XR2 connector

circuit

12

AC

11

AC

10

AC

9

 

8

 

7

input or output signals:

emergency shutdown breaker circuit REPO (jumper Y

correction with optional electric boad for

XR1

harmonic filter

XA1 terminal block

-12V

6

power supply +12V

 

5

temperature

4

signal

3

 

2

 

1

measuring battery temperature

harmonics over-temperature fault

battery-room ventilation fault

2

1

thermal measuring of the harmoinc-filter circulator

XR3 connector

 

 

 

 

input or output signals:

battery cubicle

 

-12V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

free auxilary contact

XA13 terminal block

 

 

 

 

 

 

9

-12V

 

 

 

 

 

 

 

 

 

QF1 battery

24V CC

8

 

 

 

 

 

 

2

 

 

circuit breaker

7

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

closed

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-12V

5

 

 

 

OF1 battery circuit-breaker opening command

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

QF1 battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

2

 

 

circuit breaker

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

opening command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

AC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XR4 connector

 

 

 

 

output signals:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

Optional alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

AC

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

3

 

 

 

EPO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

XR4 connector

1

 

 

 

output signals:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10AC

9

 

 

load or inverter

 

 

8

 

 

 

 

7

 

 

 

 

 

 

6

 

 

load or battery

 

 

5

 

 

 

 

4

 

 

 

3

 

 

low-battery shutdown warning

 

 

2

 

 

 

 

1

 

 

 

 

 

 

86-133060-00 A00

Installation

3 — 9