Installation and User Manual

1.8Parallel Connected UPS Units

For installations with redundant units, take into account only the units required to supply the load power (e.g. for an installation made up of 3 parallel-connected UPS units, one being redundant, only 2 UPS units are used to determine bypass AC source and load currents and cable cross-sections).

Table 1-5 serves as an example for a parallel connected installation comprising up to four UPS units.

Table 1-5: Parameters for Bypass AC Source and Load Cables for a Parallel UPS.

Parameters
rated unitnumber oftotal UPSbypass AC

output

parallel-rated outputsource or load

in kVA

connected

in kVA

line current

 

units

 

in Amps

100

2

200

240

 

 

3

300

360

 

 

4

400

480

 

130

2

260

312

 

 

3

390

468

 

 

4

520

624

 

150

2

300

360

 

 

3

450

540

 

 

4

600

720

 

180

2

360

434

 

 

3

540

651

 

 

4

720

868

 

200

2

400

482

 

 

3

600

723

 

 

4

800

964

 

225

2

450

542

 

 

3

675

813

 

 

4

900

1084

 

86-133060-00 A00

Introduction

1 — 9