Appendices
Appendix A
Front Control Panel Display Definitions1"Rectifier/charger" light◗light off: rectifier/charger OFF.
◗light shines green: rectifier/charger ON.
◗light shines red: rectifier/charger fault, the stored alarm indicates one or several of the following faults:
-input circuit breaker Q1 open,
-protection fuse at the rectifier/charger input (FUE) blown,
-abnormally high internal rectifier/charger temperature,
-abnormally high battery charge current,
-abnormally high battery voltage,
-fault,
-fault on the electronic
-abnormally high temperature in the harmonic filter inductor.
2
3
"Battery light"
◗light off: battery float charging.
◗light flashing green: battery recharging.
◗light shines green: load on battery power.
◗light flashing red:
◗light shines red: battery at end of backup time and circuit breaker QF1 open, or battery fault.
◗light off: bypass AC source within specified tolerances and static bypass open.
◗light shines green: static bypass closed.
◗light shines red: the stored alarm indicates one or several of the following faults:
-bypass AC source voltage or frequency outside specified tolerances,
-
-abnormally high internal
-
-
-fault on the electronic board controlling the transfer function,
-
-fault on the electronic
-fault on monitoring the "inverter ready" response channels (parallel UPS system).
Appendices | A — 1 |