Installation and User Manual
Appendix C
Link to an IBM AS/400® ComputerThe Galaxy PW™can dialogue with an IBM AS/400® computer via a link in compliance with IBM communications recommendations, thus enhancing the protection provided by your Galaxy PW™.
The IBM AS/400® computer must be configured for the link. This section describes the physical connections required as well as the system values that must be modified on the AS/400®. For further information, consult the following IBM documents:
◗"Planning Guide, Appendix E" concerning physical connections.
◗
Connections are made to the female client connector XR5 on the "Media Contacts 11" board. The corresponding male connector is supplied; see Figure
1.On the AS/400® side, use a 9 or
2.Certain values on the AS/400® must be configured to enable operation of the Galaxy PW™ — AS/400® link.
The values requiring modification and the corresponding procedures are presented in chapter 7 "Power Loss Recovery" of the
Configuration values:
◗QUPSMSGQ: UPS message queue;
◗QUPSDLYTIM: Uninterruptible power supply delay time;
◗QPWRRSTIPL: Power restore IPL.