Galaxy PW™ UPS 100 to 225kVA
3.7.1Battery Circuit Breaker "QF1" Connection
Connect the cable from connector XR3 (pins 2 to 8) on the "Media Contacts 11" board in the UPS cabinet to connector XR1 in the battery cabinet containing battery circuit breaker QF1.
IMPORTANT | In the case of a complex installation with parallel units, there should be only one |
| emergency shutdown pushbutton and this pushbutton must interrupt all the units. |
| This pushbutton must therefore have as many contacts as there are units in the |
| installation. The emergency shutdown pushbutton turns off the rectifier/ chargers |
| and inverters, opens the battery circuit breakers (QF1), the input circuit breaker (Q1) |
| on the normal source, the backfeed protection contactor (K4S) on the bypass AC |
| source, blocks the static switches and activates a contact on the "Media Contacts 11" |
| board (terminals 1 to 3 on connector XR4). |
|
|
3.8Installation of the "Temperature Monitor" in the Battery Cabinet
The "Temperature Monitor" unit is placed inside the battery cabinet housing
1.Open the unit cover, and before fixing, break the
2.Fix the unit on the plate using the
3.Connect and put back the cover. The temperature sensor MUST be placed at the top of the cabinet to work properly.
4.Tie the connecting cable to the cabinet upright so that it does not pull on the unit.
Figure
Battery Cabinet
QF1
to UPS Cabinet
Temperature
Monitor unit
Tie the cable to the cabinet upright
3 — 10 | Installation |