Galaxy PWUPS 100 to 225kVA

1.7Recommended Protection1.7.1Protection Upstream of Galaxy PW™

The information provided here is purely indicative, for a single UPS unit. Check that all the criteria mentioned in the previous section are taken into account (short-circuit current and protection of the static switch semiconductors on the bypass AC input).

Table 1-3: Rating Recommended for Devices Upstream of Single UPS.

Ratings
rated UPSCB on normal

 

CB on bypass

 

output

AC input

 

AC input

 

in kVA

circuit breaker

control unit

circuit breaker

control unit

100

125A

125A

125A

125A

130

160A

160A

160A

160A

150

250A

200A

250A

200A

180

250A

250A

250A

250A

200

400A

400A

400A

400A

225

400A

400A

400A

400A

1.7.2Protection Downstream of Galaxy PW™

These protection devices ensure discrimination for each of the Galaxy PW™ output circuits. If the recommended downstream protection is not installed and a short-circuit occurs, the result may be a break longer than 20-min on all the other output circuits.

Table 1-4: Rating Recommended for Devices Downstream of Single UPS.

Ratings

rated UPS

downstream circuit

 

output

breaker(s)

 

in kVA

circuit breaker

control unit

100 to 225kVA

100A

63A curve C

 

 

100A curve B

1 — 8

Introduction

86-133060-00 A00