Galaxy PW™ UPS 100 to 225kVA
The information provided here is purely indicative, for a single UPS unit. Check that all the criteria mentioned in the previous section are taken into account
Table
rated UPS | CB on normal |
| CB on bypass |
|
output | AC input |
| AC input |
|
in kVA | circuit breaker | control unit | circuit breaker | control unit |
100 | 125A | 125A | 125A | 125A |
130 | 160A | 160A | 160A | 160A |
150 | 250A | 200A | 250A | 200A |
180 | 250A | 250A | 250A | 250A |
200 | 400A | 400A | 400A | 400A |
225 | 400A | 400A | 400A | 400A |
These protection devices ensure discrimination for each of the Galaxy PW™ output circuits. If the recommended downstream protection is not installed and a
Table
Ratings
rated UPS | downstream circuit |
|
output | breaker(s) |
|
in kVA | circuit breaker | control unit |
100 to 225kVA | 100A | 63A curve C |
|
| 100A curve B |