Galaxy PW™ UPS 100 to 225kVA
3.5Connections Between Cabinets
These connections are made on the UPOZ board (marked T) and MUSI board (marked U). See Figure
These connections are made using the cables (A) supplied, see Figure
The purpose of the connection is to make a loop. Connector XM137 on the UPOZ board of one UPS unit must be connected to connector XM136 on the UPOZ board of the next UPS unit and so on until the first board is returned to origin.
Figure
'UPOZ' Galaxy PWTM 2
XM137AXM138
'UPOZ' Galaxy PWTM 3
XM137
XM138
3.5.2Connections Between UPS Cabinets and the Remote External BypassRefer to the installation drawing included with the Maintenance Bypass Cabinet for control and power connections. These connections are provided and installed by the user.
3 — 4 | Installation |