GAS APPLIANCE INSTALLATION
8.Be sure the gas is turned off at the appliance, then turn the gas on at the cut off valve and test the gas line connections for leaks with soapy water solution or a liquid leak detector. DO NOT USE A MATCH OR OTHER FLAME SOURCE TO CHECK FOR GAS LEAKS. If a gas leak is detected, turn the gas off immediately and fix the leak.
9.Proceed with testing the appliance for leaks and adjusting it as required by the manufacturer instructions.
FIGURE 28
GAS LINE PLUMBING DETAIL
OUTER FIREPLACE WRAP INNER FIREPLACE WRAP
SIDE BRICK
26" MAX.
FIREPLACE FIREBOX
HEARTH BRICK GAS LINE ACCESS TUBE
BACK
REFRACTORY
BRICK
MAINTAIN 1/2" MINIMUM
AIR SPACE CLEARENCE
TO COMBUSTIBLES FOR
GAS LINE OUT TO 4" FROM
SIDE OF THE FIREPLACE.
COMBUSTIBLE MATERIALS
MAY BE LOCATED AT ZERO
CLEARANCE TO GAS LINEKNOCKOUT BEYOND 4" FROM FIREPLACE
SIDE.
SIDE
REFRACTORY
BRICK
CAUTION: WHEN USING A GAS APPLIANCE, THE FIREPLACE DAMPER MUST BE SET IN FULLY OPEN POSITION.
REPACK INSULATION AROUND
GAS LINE WHERE IT PASSES THRU GAS LINE ACCESS TUBE FOR
PROPER SEAL.
APPLYING DECORATIVE TRIM TO THE FIREPLACE
Do not allow the trim materials to extend closer than 3/8 inch to the vertical edges of the firebox opening if you plan to equip the fireplace with glass doors.
The face of your fireplace may be left exposed or trimmed with any noncombustible material such as brick, stone or marble. See Figure 29. If a trim is installed, be sure it is fastened snugly to the face of the fireplace. A crack between the material and the face of the fireplace could pose a fire hazard and impair the proper operation of the fireplace. Blocking the fireplace with framing and attaching the base to the supporting floor will further reduce the possibility of such a crack developing.
Wall ties should be fastened to the face of the fireplace with sheet metal screws and placed in the mortar joints of masonry trim.
Combustible material must not be installed below the top spacers of the fireplace or overlap the sides of the fireplace face. Figures 30 and 31. Seal the face of the fireplace to the surrounding wall with
The trim should not block or restrict in any way the flow of air into the side air inlets in the face of the fireplace.
Be sure to provide the required floor protection as described in a preceding section of this manual.
Combustible mantles and trim must be installed in accordance with the National Fire Protection Association - ANSI NFPA 211 Standard - Section
26
53D9032. Rev 1 03/03