100 Mb Fiber Transceiver Characteristics

Fiber Length

2km*

15km**

40km**

80km**

 

 

 

 

 

TX Power Min

-19dBm

-15dBm

-5dBm

-5dBm

 

 

 

 

 

RX Sensitivity Max

-31dBm

-31dBm

-34dBm

-34dBm

 

 

 

 

 

Wavelength Min/Max

1310nm

1310dm

1310dm

1550nm

 

 

 

 

 

*Multimode Fiber Optic Cable

**Singlemode Fiber Optic Cable

Gigabit Fiber Transceiver Characteristics

Fiber Length

550m* with

300m* with

10km**

40km**

80km**

50/125 µm

62.5/125 µm

 

 

 

 

 

 

 

 

 

 

 

TX Power Min

-9.5dBm

-9.5dBm

-5dBm

-4dBm

-3dBm

RX Sensitivity

-17dBm

-17dBm

-20dBm

-21dBm

-23dBm

Max

 

 

 

 

 

Wavelength

850nm

850nm

1310nm

1550nm

1550nm

Assumed

-3.5 dB/km

-3.75 dB/km

-0.5 dB/km

-0.25 dB/km

-0.20 dB/km

Fiber Loss

 

 

 

 

 

Laser Type

VCSEL

VCSEL

FP

DFB

DFB

*SX Fiber Optic Cable ** LX Fiber Optic Cable

Regulatory Approvals:

Safety: Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations, or Nonhazardous Locations only.

EMI: EN61000-6-4, EN55011 – Class A

FCC Title 47, Part 15, Subpart B - Class A

EMS: EN61000-6-2

EN61000-4-2 (ESD)

EN61000-4-3 (RS)

EN61000-4-4 (EFT)

EN61000-4-5 (Surge)

EN61000-4-6 (Conducted Disturbances)

Conducted Low Frequency: IEC60533

Shock: IEEE 1613 (250 mm)

Vibration: IEEE 1613 (V.S.3 20 mm/s)

IEC60068-2-6 (Test Fc)

Cold: IEC60068-2-1

Dry Heat: IEC60068-2-2

Damp Heat: IEC60068-2-30 (Test Db)

GOST-R Certified.

Warranty: Effective January 1, 2008, all N-TRON products carry a 3 year limited warranty from the date of purchase.

(Revised 2010-7-2)

page 144 of 145

Page 144
Image 144
N-Tron 9000 user manual Mb Fiber Transceiver Characteristics