Napco Security Technologies XP-400 Telephone Number 3 Programming, Report Codes, 62Zone Codes

Models: XP-400

1 28
Download 28 pages 54.33 Kb
Page 18
Image 18
Telephone Number 3 Programming

WI1370 XP-400 Installation Instructions

Telephone Number 3 Programming

[50] - [59]

Programming is the same as for Telco 1. Program to split/double report to Telco 3. Refer to sections [30] through [39].

Report Codes

[60]Zone Report Codes

Report Code for Zones 1 through 4.

4/2 format - The Zone Report Code is the 1st digit of the report code sent, the second digit is the zone number of the reporting zone. For example, if zone 2 has a reportcode of 3, the report code would be 32.

3/1 format - Sends only the report Code and does not append it with the zone number.

[61]Point ID Report Codes

Point ID Report Codes are defaulted to Burglary for zones 1 through 4. Optionally, Point ID codes for zones 1 through 4 can be programmed as follows:

[1]

Reserved

[7] Gas Alarm

[2]

Panic

[8]

Heat Alarm

[3]

Burglary

[9]

Reserved

[4]

Holdup

[A] Auxiliary

[5] General Alarm

[B] 24 Hour

[6]

Reserved

 

 

[62]Zone Codes

[62-1] Restore code - Zones 1 through 8. The second digit of the restore code is the zone number of the restored zone. For example, if the Zone Restore Code [62] is programmed to E, the restore code for that zone would be E4 (4/2 format).

[62-2] Trouble Code - Conditional Closing Reports. Zones that are bypassed at the time of arming send this code along with the zone number of the bypassed zone(s). For example a conditional closing by User 2, with zones 2 and 3 bypassed would be as

follows: 1234 C2 F2 F3

[63]System Report Codes

Program a 2-digit report code for Keypad Panic 2, Keypad AUX, Keypad Panic, Test Timer, AC Fail, Low Battery and Trouble.

[64]System Restore Code

The code sent when a system condition restores. The second digit of the 2-digit restore code is the second digit of the System Report Code [63]. For example, if a Low Battery System Report Code is F8 the Battery Restore would be E8 (4/2 format).

[65]Opening and Closing Codes

Program Opening and Closing Codes for Users 1 through 4. The second digit of the report code is the number of the user that armed or disarmed the system. For example, if the Closing Code [65] is programmed with a C, the closing code for User 2 would be C2 (4/2 format).

18

Page 18
Image 18
Napco Security Technologies Telephone Number 3 Programming, Report Codes, WI1370 XP-400Installation Instructions