[03]Auto-Bypass Reentry Zones

WI1370 XP-400 Installation Instructions

To eliminate this fixed 20-second entry delay, also program zones as Exit/Entry Follower Zones [02].

To return protection to zones of this type, press cb from the keypad or Mor

N from a Keyfob. Program the Keyfob AUX 1 or AUX 2 button for Full Set [81-7].

NOTE:

Auto Interior Bypassing - Also program zones as Home/Away with Delay Zone(s) [01] to automatically bypass at the expiration of the exit delay if the EXIT/ENTRY Zone(s) are not violated during the exit delay.

[03]Auto-Bypass Reentry Zones

Zones programmed as this zone type are

[06]Open Circuit Zones

Program this zone type if unsupervised normally open circuit devices are required The programming option is not permitted for UL installations.

Normally Open Zone Wiring

If A0 is Entered during Exit Time, Home/

Away with Delay Zones will be automatically bypassed, even if the Exit/Entry Zone is violated. Easy Exit/Easy Arm [22-2] must be enabled.

[02]Exit/Entry Follower Zones

Entry Delay allows the user time to enter and disarm. Allows exit after the panel is armed without setting off an immediate alarm and allows entry only if an Exit/Entry

permitted to be faulted at the time of arming. Once the zone is restored, while the control panel is still armed, the zone will automatically be unbypassed and any subsequent violations of the zone will cause an alarm condition.

[04]24-Hour Protection

Wire the normally open contact

as shown (Zone 4). EZ Zone DoublingTM resistor

is required. Program the zone for

Open Circuit [06].

9.3K (Z)

 

ZONE 4

2

(E)

.2K

 

ZONE 1

Zone [00] has been violated first. Zones of this type have a three (3) minute power-up delay, and do not display or cause an alarm if faulted when the system powers up. Pressing the b key cancels the 3 minute timer.

Group Bypassing - Zones programmed as Exit/Entry Follower Zones will be Group bypassed if the ccis pressed while disarmed or within the Exit Delay.

A zone that provides protection at all times, whether or not the system is armed.

[05]40 ms Loop Response

Normally loop response is 750 ms, select this option to change the loop response to 40 ms. The slower the loop response, the less sensitive the system will be to intermittents (swingers). The programming option is not permitted for UL installations.

FIGURE 5 OPEN CIRCUIT WIRIING

[07]Burg (Steady) Output

Enables the Bell Output on a zone trip for each zone selected. The Bell Output will remain ON for the length of time

programmed for Burg (Steady) Output [07]

or it will remain ON until turned off by entering a valid Arm/Disarm Code; 0 means output will stay ON until reset.

12

Page 12
Image 12