BGD36CF(G) TOP OR REAR EXIT VERTICAL TERMINATION

when (HT) < (VT)

Simple venting confi guration (only two 90° elbows)

FIGURE 29

REQUIRED

VERTICAL

RISE IN

FEET VT

HORIZONTAL VENT RUN PLUS

OFFSET IN FEET HT

The shaded area within the lines represents acceptable values for HT and VT .

See graph to determine the required vertical rise VT for the required horizontal run HT

For vent confi gurations requiring more than zero 90° elbow (top exit) or one 90° elbow (rear exit), the following formulas apply:

Formula 1: HT < VT

Formula 2: HT + VT < 40 feet

Example 6:

90° V2

FIGURE 30

H2

H1 V1

90°

V1=5 ft

90°

 

V2=10 ft

VT=V1 + V2 = 5 + 10 = 15 ft H1=3 ft

H2=2.5 ft

HR=H1 + H2 = 3 + 2.5 = 5.5 ft HO=.03 (three 90° elbows - 90°)

=.03(90 + 90 + 90 - 90) = 5.4 ft

HT=HR + HO = 5.5 + 5.4 = 10.9 ft

HT + VT= 10.9 + 15 = 25.9 ft

Formula 1: HT < VT 10.9 < 15

Formula 2: HT + VT < 40 feet 25.9 < 40

Since both formulas are met, this vent confi guration is ac- ceptable.

when (HT) > (VT)

Simple venting confi gurations

FIGURE 31

See graph to determine

the required vertical rise VT for the required horizontal

run HT.

MAXIMUM

VERTICAL

RISE IN

FEET

VT

HORIZONTAL VENT RUN PLUS OFFSET IN

FEET HT

The shaded area within the lines represents acceptable values for HT and VT .

For vent confi gurations requiring more than two 90° elbows (top exit) or one 90° elbow (rear exit), the following formulas apply:

Formula 1: HT < 3VT

Formula 2: HT + VT < 40 feet

Example 7:

90°

90°

V3

V1

V2 H2

 

 

H1

90°

 

90°

FIGURE 32

V1 = 2 ft V2 = 1 ft V3 = 1.5 ft

VT = V1 + V2 + V3 = 2 + 1 + 1.5 = 4.5 ft H1 = 6 ft

H2 = 2 ft

HR = H1 + H2 = 6 + 2 = 8 ft

HO = .03 (four 90° elbows - 90°)

= .03(90 + 90 + 90 + 90 - 90) = 8.1 ft

HT = HR + HO = 8 + 8.1 = 16.1 ft

HT + VT = 16.1 + 4.5 = 20.6 ft

Formula 1: HT < 3VT

3VT = 3 x 4.5 = 13.5 ft

Since this formula is not met, this vent confi guration is unac- ceptable.

Formula 2: HT + VT < 40 feet 20.6 < 40

Since only formula 2 is met, this vent confi guration is unacceptable and a new fi replace location or vent confi guration will need to be established to satisfy both formulas.