Napoleon Fireplaces BGD36CFGN, BGD42CFN, BGD36CFNTR BGD36CFG TOP OR REAR EXIT VERTICAL TERMINATION

Models: BGD42CFN BGD36CFNTR BGD36CFGN

1 48
Download 48 pages 29.33 Kb
Page 15
Image 15
Manual background

15

BGD36CF(G) TOP OR REAR EXIT VERTICAL TERMINATION

Example 8:

90°

45°

V2

V H2

 

H3

90°

1

H1

 

 

90°

 

FIGURE 33

V1 = 1.5 ft

V2 = 5 ft

VT = V1 + V2 = 1.5 + 5 = 6.5 ft H1 = 1 ft

H2 = 1 ft

H3 = 10.75 ft

HR = H1 + H2 + H3 = 1 + 1 + 10.75 = 12.75 ft

HO = .03 (three 90° elbows + one 45° elbow - 90°) = .03(90 + 90 + 90 + 45 - 90) = 6.75 ft

HT = HR + HO = 12.75 + 6.75 = 19.5 ft

HT + VT = 19.5 + 6.5 = 26 ft

Formula 1: HT < 3VT

3VT = 3 x 6.5 = 19.5 ft

19.5< 19.5

Formula 2: HT + VT < 40 feet

26 < 40

Since both formulas are met, this vent confi guration is accept- able.