Napoleon Fireplaces BGD36CFNTR, BGD36CFGN, BGD42CFN manual Vertical Installation, b

Models: BGD42CFN BGD36CFNTR BGD36CFGN

1 48
Download 48 pages 29.33 Kb
Page 20
Image 20
BGD42CF ONLY

20

FIGURE 48

BGD42CF ONLY

ADJUSTABLE FIRESTOP INSTALLATION

Apply a bead of caulking all around the edge of the opening and place the fi restop top, so that the vent shield covers the top of the vent within the opening.

The length of the vent shield may be cut shorter for combustible walls that are less than 8 1/2" thick but the vent shield must extend the full depth of the combustible wall.

Place the fi restop bottom against the fi restop top and secure the two together. Adjust the assembly to ensure it is tight to the vent. Secure fi restop to wall. Ensure that both spacer and shield main- tain the required clearance to combustibles. Once the vent pipe is installed in its fi nal position, apply sealant between the vent pipe and the fi restop spacer. This restricts cold air from being drawn into the room or around the fi replace. See Figures 49a-c.

VENT SHIELD

FIGURE 49a

FIRESTOP TOP

FIRESTOP BOTTOM

FIGURE 49b

FIGURE 49c

Where the opening in the outside wall has been cut 13" tall to provide 2" clearance from the vent pipe, terminal extension plate W500-0206 must be used to cover the opening.

VERTICAL INSTALLATION

1.Determine the air terminal location, cut and frame 9 3/4" for the BGD36CF(G), or 10 3/4" for the BGD42CF square opening in the ceiling and an opening in the roof to provide the minimum 1" clearance between the fi replace vent pipe and any combustible material. Try to center the exhaust pipe location midway between two joists to prevent having to cut them. Use a plumb bob to line up the center of the openings.

DO NOT FILL THIS SPACE WITH ANY TYPE OF MATERIAL.

A vent pipe shield will prevent

 

any materials such as insula-

 

tion, from fi lling up the 1" air

BGD36CF(G) = 9 3/4”

space around the pipe. Nail

headers between the joist for

BGD42CF = 10 3/4”

extra support.

 

2.Apply a bead of caulking

(not supplied) to the frame- work or to the Wolf Steel vent pipe shield plate or equivalent (in the case of a fi nished

FIGURE 50

ceiling), and secure over the opening in the ceiling. A

restop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through.

Apply a bead of caulking all

around and place a fi restop

spacer over the vent shield toFIGURE 51 restrict cold air from being drawn

into the room or around the fi replace. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its fi nal

position, apply high temperature sealant W573-0002 (not sup- plied) between the vent pipe and the fi restop spacer.

3.In the attic, slide the vent pipe collar down to cover up the open end of the shield and tighten.

This will prevent any materials, such as insulation, from fi lling up the 1" air space around the pipe.

FIGURE 52

W415-0661 / C / 02.20.08

Page 20
Image 20
Napoleon Fireplaces BGD36CFNTR, BGD36CFGN, BGD42CFN Vertical Installation, BGD42CF ONLY ADJUSTABLE FIRESTOP INSTALLATION, b