[Connections and Settings in Torque Control Mode]

Signal

Pin No.

Symbol

 

 

 

 

 

Function

I/F circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

Command pulse

33

INH

 

The function differs depending on the control mode.

SI

input inhibit

 

 

 

 

 

 

 

 

 

 

 

 

page 134

 

Position control

 

• Enter command pulse input inhibit.

 

 

 

 

 

 

 

 

 

 

 

• You can disable this input with Pr43

 

 

 

 

 

 

 

(disable command pulse input inhibit).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr43 value

Meaning

 

 

 

 

 

 

 

 

 

 

1(Factory-setting)

The INH signal (input) is disabled.

 

 

 

 

 

 

 

 

 

 

 

0

• With COM– closed, the pulse

 

 

 

 

 

 

 

 

 

 

 

 

 

command signal (PULSE SIGN) is

 

 

 

 

 

 

 

 

 

 

 

 

 

enabled.

 

 

 

 

 

 

 

 

 

 

 

 

 

• With COM– open, the pulse

 

 

 

 

 

 

 

 

 

 

 

 

 

command signal (PULSE SIGN) is

 

 

 

 

 

 

 

 

 

 

 

 

 

inhibited.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed control

 

• With speed setting of the 1st selection input, you can set 4

 

 

 

 

 

 

 

speeds in combination with CL input.

 

 

 

 

 

 

 

• For details, see Pr05 (Speed Set-Up Switching) description.

 

 

 

 

Torque control

 

• Invalid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speed zero clamp

26

ZEROSPD

• With COM– open, the speed command is considered zero.

SI

 

 

 

 

 

 

• This input can be made disabled using Pr06.

page 134

 

 

 

 

 

 

• With factory setting, disconnecting this pin from COM– sets

 

 

 

 

 

 

 

 

the speed to zero.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr06 value

Meaning

 

 

 

 

 

 

 

 

 

 

0 (Factory-setting)

ZEROSPD is disabled.

 

 

 

 

 

 

 

 

 

 

 

1

ZEROSPD is enabled.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gain switching

27

GAIN

 

• This is setting of Pr30 (2nd gain setting) and has the

SI

 

 

 

 

 

 

 

following 2 types of functions:

page 134

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr30 value

 

Connection

 

 

Function

 

 

 

 

 

to COM-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

Open

 

Speed loop: PI (Proportional / Integral) action

 

 

 

 

(Factory-setting)

 

 

Close

 

Speed loop: P (Proportional) action

 

 

 

 

 

 

 

 

Open

 

• 1st gain selected (Pr10, 11, 12, 13 and 14)

 

 

 

 

 

1

 

 

Close

 

• 2nd gain selected (Pr18, 19, 1A, 1B, 1C)

 

 

 

 

 

 

 

To use the second gain, set Pr31 to “2”.

 

 

 

 

 

 

 

 

• No.2 Gain change Funcutions, see page 202 "Adjustments ".

 

Alarm clear

31

A-CLR

 

• If the COM- connection is kept closed for more than 120

SI

 

 

 

 

 

 

 

ms, the alarm status will be cleared.

page 134

 

 

 

 

 

 

• For details about not cleared alarm, see page 216

 

 

 

 

 

 

 

 

"Protective Functions".

 

Torque Control Mode

Connections and Settings in

137

Page 7
Image 7
Panasonic MINAS A3 Series manual Inh, Zerospd, Gain, Clr