Quadra-Fire CASTILEI-MBK owner manual Vent Information, 4Castile Pellet Insert

Models: CASTILEI-MBK

1 56
Download 56 pages 60.57 Kb
Page 13
Image 13
4Castile Pellet Insert

R

4Vent InformationA. Chimney and Exhaust ConnectionB. Venting Termination RequirementsS629M, STANDARD FOR 650oC FACTORY-BUILT CHIMNEYS.Manual backgroundCastile Pellet Insert

Vent Information

A. Chimney and Exhaust Connection

1.Chimney & Connector: Use 3 or 4 inch (76-102mm) diameter type "L" or "PL" venting system. It can be vented vertically or horizontally.

2.Mobile Home: Approved for all Listed pellet vent. Use Listed double wall flue connector. A Quadra-Fire outside air kit must be used with manufactured home installations.

3.Residential: Use 24 gauge single wall fl ue connector or Listed double wall fl ue connector to Class A Listed metal chimneys, or masonry chimneys meeting International Build- ing Code (ICC) standards for solid fuel appliances.

4.INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.

5.Secure exhaust venting system to the appliance with at least 3 screws. Also secure all connector pipe joints with at least 3 screws through each joint.

6.DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.

7.DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.

NOTE: All pipe must be welded seam pipe whenever pos- sible. Seal pipe joints with high temperature silicone (500°F [260°C] minimum rated only).

B. Venting Termination Requirements

CAUTION

Do not terminate vent in any enclosed or semi-enclosed area such as a carport, garage, attic, crawl space, under a sun deck or porch, narrow walkway or closely fenced area, or any location that can build up a concentration of fumes such as a stairwell, covered breezeway, etc.

1. Termination must exhaust above air inlet elevation. It is strongly recommended that at least 60 inches (1524mm) of vertical pipe be installed when appli- ance is vented directly through a wall. This will create a natural draft, which will help prevent the possibility of smoke or odor venting into the home during a power outage. It will also keep exhaust from causing a nui- sance or hazard by exposing people or shrubs to high temperatures. The safest and preferred venting method is to extend the vent vertically through the roof.

2. Distance from doors and opening windows, or gravity or ventilation air inlets into building:

a.Not less than 48 inches (1219mm) below;

b.Not less than 48 inches (1219mm) horizontally from;

c.Not less than 12 inches (305mm) above.

NOTE: If burning shelled field corn, you must use approved venting specifically designed for corn. Follow the instruc- tions from the venting manufacturer.

WARNING

Fire Risk.

Only LISTED venting components may be used.

NO OTHER vent components may be used. Substitute or damaged vent components may impair safe operation.

Follow venting manufacturer’s clearances and instructions when installing venting system.

Manual background WARNING

Vent surfaces get HOT, can cause burns if touched. Non-combustible shielding or guards may be required.

NOTICE: In Canada when using a factory-built chim- ney it must be safety listed, Type UL103 HT (2100oF) [1149oC] CLASS “A” or conforming to CAN/ULC-

S629M, STANDARD FOR 650oC FACTORY-BUILT CHIMNEYS.

3. Distance from permanently closed windows:

a.Not less than 12 inches (305mm) below, horizontally from or above.

4. Distance between bottom of termination and grade should be 12 inches (305mm) minimum. This is con- ditional upon plants in the area, and nature of grade surface. The grade surface must be a non-combustible material (i.e., rock, dirt). The grade surface must not be lawn. Distance between bottom of termination and public walkway should be 84 inches (2134mm) minimum.

5. Distance to combustible materials must be 24 inches (610mm) minimum. This includes adjacent buildings, fences, protruding parts of the structure, roof overhang, plants and shrubs, etc.

6.Termination Cap Location (Home Electrical Service)

Side-to-side clearance is to be the same as minimum clearance to vinyl inside corners.

Clearance of a termination cap below electrical service shall be the same as minimum clearance to vinyl sof- fi ts.

Clearance of a termination cap above electrical service will be 12 inches (305mm) minimum.

Location of the vent termination must not obstruct or interfere with access to the electrical service.

January 19, 2011

7022-122

Page 13