Quadra-Fire CASTILEI-MBK C. Masonry and Factory-BuiltFireplaces, F. Prefabricated Metal Chimney

Models: CASTILEI-MBK

1 56
Download 56 pages 60.57 Kb
Page 11
Image 11
C. Masonry and Factory-Built Fireplaces

R

C. Masonry and Factory-Built Fireplaces

Maximum Mantel Depth: 12 inches (305mm)

 

Face

Mantel

 

Trim

 

 

B

C

 

 

 

 

 

 

 

 

Side Wall

 

 

 

 

 

A

 

 

D

 

 

F

 

E

 

 

 

Figure 11.1

 

 

 

 

 

 

 

 

Inches

Millimeters

A

Insert side to combustible side wall

16

406

B

Insert top to mantel

 

 

12

305

C

Insert top to maximum. 2-1/4 inch

4-3/4

121

 

(57mm) face trim

 

 

 

 

D

Insert side to maximum. 2-1/4 inch

10

254

 

(57mm) face trim

 

 

 

 

D. Minimum Opening for Masonry and Factory-Built Fireplaces

B

C

A

 

 

D

Figure 11.2

 

Location

Inches

Millimeters

A

Rear Width

23-5/8

600

B

Depth

17

432

C

Height

21-1/4

540

D

Front Width

28-1/8

714

Castile Pellet Insert

E. Floor Protection

 

 

Inches

Millimeters

E

Floor protection hearth extension from

6

152

 

door opening

 

 

 

F

Floor protection to the side of door

6

152

 

opening

 

 

F. Prefabricated Metal Chimney

The chimney can be new or existing, masonry or prefabricated and must meet the following minimum requirements:

•Must be minimum 6 inch (152mm) inside diameter of high temperature chimney listed to UL 103 HT (2100oF) or ULC-S628.

•Must use components required by the manufacturer for installation.

•Must maintain clearances required by the manufacturer for installation.

•Refer to manufacturers instructions for installation

•This insert is listed to UL 1482 Standard and is approved for installation into listed factory-built zero clearance fire- places listed to UL 127 conforming to the following speci- fi cations and instructions:

•The original factory-built zero clearance fi replace chim- ney cap must be re-installed after installing the approved chimney liner meeting type UL 103 HT requirements (2100°F) per UL 1777.

•If the chimney is not listed as meeting HT requirements, or if the factory built fi replace was tested prior to 1998, a full height listed chimney liner must be installed from the appliance fl ue collar to the chimney top.

•The liner must be securely attached to the insert flue collar and the chimney top.

•The air fl ow of the factory-built zero-clearance fi replace system must not be altered. The fl ue liner top support attachment must not reduce the air fl ow for the existing air-cooled chimney system.

•No dilution air is allowed to enter the chimney.

1.Secure the fi replace damper in the open position. If this cannot be accomplished, it will be necessary to remove the damper.

2.Seal damper area of chimney around chimney connector with a high temperature sealant or seal insert against the face of the fi replace.

3.Both methods must be removable and replaceable for cleaning and re-installation.