INSTALLATION

UNIT ASSEMBLY

PRIOR TO INSTALLATION

The Top Facing Support, the Side Nailing Strips and the 2 Top Standoffs must be correctly po- sitioned and attached to the top before the unit is put into position.

Top Standoff Assembly

The top standoffs are shipped in a fl at position and must be pulled up and bent into the cor- rect shape.

1)Remove the standoffs from on top of the fi rebox by undoing the screws.

2)Take each standoff and bend into the cor- rect shape. Bend up at the bend lines until the screw holes in the standoff and the pre-punched screw holes on the fi rebox top line-up.

3)Attach the standoffs securely to the top with 4 screws per standoff.

Note: Secure the standoffs to the holes closest to the edge of the fi rebox top.

Top Facing Support &

Side Nailing Strips

Determine the total thickness of facing mate- rial (e.g. drywall plus ceramic tiles) to allow the

nished surface to be fl ush with the front of the unit. Total facing thickness can vary from 1/2" (13mm) to 1-1/4" (32mm) thick.

The Top Facing Support & Side Nailing Strips can be mounted in various positions depending on the thickness of the facing material.

1)Mount Top Facing Support using the 3 supplied screws into the three pre-punched screw holes on the top front of the unit.Adjust support to desired facing material depth.

2)Mount Side Nailing Strip using the 3 sup- plied screws into the three pre-punched screw holes at the front sides of the unit. Adjust support to desired facing material thickness.

For a facing material depth of 1-1/4"(32mm), the top facing support must be reversed.

VENTING INTRODUCTION

The P33-3 uses the "balanced fl ue" technology Co Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.

There are 2 vent systems approved for use with the P33-3: the Regency Direct Vent System (Flex) for Horizontal Terminations only (see pages 11-12), and the Simpson Dura-Vent Systems for Horizontal and Vertical Terminations (see pages 13-24).

Note: These flue pipes must not be connected to any other appliance.

The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.

NOTE: Ensure compliance with the outside vent terminal location before cutting hole as both dimensions must be met.

Regency P33-3 Zero Clearance Direct Vent Gas Fireplace

Page 9
Image 9
Regency P33-NG3, P33-LP3 Unit Assembly Prior to Installation, Venting Introduction, Top Standoff Assembly