Reference for air-discharge chamber (field supply)

Reference for air-discharge chamber (field supply)

Required space around outdoor unit

CHX03652/06052

If an air discharge chamber is used, the space shown below must be secured around the outdoor unit.

If the unit is used without the required space, a protective device may activate, preventing the unit from operating.

(1) Single-unit installation

9-3/8

Min. 7-7/8

Min. 3

 

Unit: in.

CAUTION

(2) Multiple-unit installation

The top and both sides must remain open.

If there are obstacles to the front and rear of the outdoor unit, the obstacle at either the front or rear must be no taller than the height of the outdoor unit.

Installation in lateral rows

More than 11-13/16

More than 7-7/8

More than 11-13/16

More than 15-3/4

Unit: in.

CAUTION

The front and top must remain open.

The obstacles must be no taller than the height of the outdoor unit.

Installation in front-rear rows

Installation with intakes facing

Installation with intakes facing outlets

intakes or outlets facing outlets

 

More than 15-3/4

 

More than 59-1/16

More than 78-3/4

CAUTION

Unit: in.

The front and both sides must remain open.