Sanyo 85464359981002 How To Process Tubing, Connecting the Refrigerant Tubing, Fig

Models: 85464359981002

1 90
Download 90 pages 27.37 Kb
Page 61
Image 61
6. HOW TO PROCESS TUBING

6. HOW TO PROCESS TUBING

6-1. Connecting the Refrigerant Tubing

Use of the Flaring Method

Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.

Flaring Procedure with a Flare Tool

(1)Cut the copper tube to the required length with a tube cutter. It is recommended to cut approx. 1 – 2 ft. longer than the tubing length you estimate.

(2)Remove burrs at the end of the copper tube with a tube reamer or file. This process is important and should be done carefully to make a good flare.

(Fig. 6-1)

NOTE

When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 6-2)

(3)Remove the flare nut from the unit and be sure to mount it on the copper tube.

(4)Make a flare at the end of copper tube with a flare tool.* (Fig. 6-3)

(*Use “RIGID®” or equivalent.)

NOTE

A good flare should have the following characteristics:

inside surface is glossy and smooth

edge is smooth

tapered sides are of uniform length

Deburring

Before

After

Fig. 6-1

Copper tubing

Reamer

Fig. 6-2

Flare nut

Copper tubing

Flare tool

Fig. 6-3

61

Page 61
Image 61
Sanyo 85464359981002 How To Process Tubing, Connecting the Refrigerant Tubing, Use of the Flaring Method, Fig