Sanyo 85464359981002 unit is installed 1-10.Check of Limit Density, Pay special attention to any

Models: 85464359981002

1 90
Download 90 pages 27.37 Kb
Page 13
Image 13
unit is installed.

Always check the gas density WARNING limit for the room in which the

unit is installed.

1-10. Check of Limit Density

When installing an air conditioner in a room, it is neces- sary to ensure that even if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room.

If the density could exceed the limit level, it is necessary to provide an opening between the unit and the adjacent room, or to install mechanical ventilation which is inter- locked with the leak detector.

(Total refrigerant charged amount: oz)

(Min. indoor volume where the indoor unit is installed: ft.3)

<Limit density 0.3 (oz/ft.3)

The limit density of refrigerant which is used in this unit is 0.3 oz/ft.3 (ISO 5149).

The shipped outdoor unit comes charged with the amount of refrigerant fixed for each type, so add it to the amount that is charged in the field. (For the refrigerant charge amount at shipment, refer to the unit’s nameplate.)

CAUTION

Pay special attention to any

 

location, such as a basement,

 

 

etc., where leaking refrigerant

 

can accumulate, since refrig-

 

erant gas is heavier than air.

1-11. Installing Distribution Joint

(1)Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed with the optional distribution joint kit (APR-P160BA).

(2)In order to prevent accumulation of refrigerant oil in stopped units, if the main tubing is horizontal then each branch tubing length should be at an angle that is greater than horizontal. If the main tubing is vertical, provide a raised starting portion for each branch.

(3)If there are height differences between indoor units or if branch tubing that follows a distribution joint is connect- ed to only 1 unit, a trap or ball valve must be added to that distribution joint. (When adding the ball valve, locate it within 1.3 ft. of the distribution joint.)

(Consult with SANYO separately concerning the ball valve.)

If a trap or ball valve is not added, do not operate the system before repairs to a malfunctioning unit are completed. (The refrigerant oil sent through the tubing to the malfunctioning unit will accumulate and may damage the compressor.)

Minimum indoor volume & floor area as against the amount of refrigerant is roughly as given in the following table.

 

ft.3

 

 

 

 

 

 

 

 

 

 

 

 

 

ft.2

 

 

 

10000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1136

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1079

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9000

 

Range below

 

 

 

 

 

 

 

 

 

1022

 

h)

 

 

 

 

 

 

 

 

 

 

 

 

 

8500

 

the density limit of

 

 

 

 

 

 

966

 

g

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

areafloordoorni.nMi

ft.8.8singceilithenhi

meuvoldoorni.nMi

3500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

398

 

8000

 

0.3 oz/ft.3

 

 

 

 

 

 

 

 

 

909

 

 

 

7500

 

 

 

 

 

 

 

 

 

 

852

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7000

 

(countermeasures

 

 

 

 

 

 

795

 

 

 

 

 

 

 

 

 

 

 

 

 

6500

 

not needed)

 

 

 

 

 

 

 

 

 

738

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

682

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

625

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

568

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

511

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

454

 

(whe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

284

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3000

 

 

 

 

 

 

Range above

 

 

341

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

 

 

 

 

 

 

the density limit of

 

 

227

 

 

 

 

 

 

 

 

 

0.3 oz/ft.3

 

 

 

 

 

 

 

1500

 

 

 

 

 

 

 

 

 

 

170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

 

(countermeasures

 

 

114

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

 

 

 

 

 

needed)

 

 

 

 

57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

500

1000

1500

2000

2500

3000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

oz

 

 

Total amount of refrigerant

Tube branching methods (horizontal use)

 

 

°

 

to

30

15

 

 

 

 

B

B A

Horizontal A

line View as seen

from arrow

Arrow view

Types of vertical trap specifications

(When using ball valve)

Main tubing

Ball valve

Indoor unit (more than 2 units)

(If only 1 unit is connected,

(BV: purchased

a ball valve is also needed on this side.)

separately)

 

 

Indoor unit (1)

 

(When not using ball valve)

Main tubing

Horizontal

 

 

(Each unit is connected to

 

Indoor unit

 

 

tubing that is either level

 

Branch tubing is

or is directed downward.)

 

directed upward.

 

More than

8in.

Indoor unit is directed downward

13

Page 13
Image 13
Sanyo 85464359981002 installation instructions unit is installed 1-10.Check of Limit Density, Pay special attention to any