8-2. Test Run Procedure
Items to Check Before the Test Run
<Outdoor unit control PCB> Unit No. setting switch (S004)
Recheck the items to check before the test run.
Set the No. of indoor units.
1.Turn the remote power switch on at least 5 hours before the test, in order to energize the crank case heater.
2.Turn the outdoor service valves (2 locations) to the
●Use caution when making the settings. If there are duplicated system addresses, or if the settings for the Nos. of the indoor units are not consistent, an alarm will occur and the system will not start.
●These settings are not made on the indoor unit PCB.
Are the
(Check the link wiring.) connected to more than 1 refrigerant system?
NO CASE 1
<Outdoor unit control PCB> |
| YES |
| |
Unit No. setting switch |
| Set the system address. |
| |
(S002 and S003) |
|
| ||
|
|
|
| |
|
|
|
| |
|
| When multiple outdoor units exist, disconnect the terminals | ||
Refer to Fig. | extended from the shorted plugs (CN33) at all outdoor main unit | |||
| PCBs except for 1. |
| ||
|
|
| ||
|
| Alternatively, move the sockets to the OPEN side. |
| |
|
|
| YES CASE 2 | |
|
|
|
| |
|
| Is it possible to turn ON the power only | ||
|
| for the 1 refrigerant system where the |
| |
|
| test run will be performed? |
|
Turn ON the indoor and
NOoutdoor unit power for that refrigerant system only.
NO
CASE 3B
Is it OK to start the compressors?
Turn ON the indoor and outdoor unit power.
*2
Will automatic address setting be |
|
| Make necessary corrections. | ||||||||
performed in Heating mode? |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| on the outdoor unit PCB for 1 second or longer, | ||||
|
|
|
|
|
|
|
|
| |||
| YES | CASE 3A |
| Turn OFF the indoor and |
| then release it. | |||||
|
|
|
|
| |||||||
|
|
| outdoor unit power |
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
Is it OK to start the compressors? |
|
|
|
|
|
|
| LED 1 and 2 blink alternately | |||
|
| Check the alarm contents. |
|
| (about 2 or 3 minutes). | ||||||
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
Turn ON the indoor and |
|
|
|
|
| NO |
|
|
| ||
outdoor unit power. |
|
|
|
|
|
| Are LEDs 1 and 2 on the | ||||
*2 |
|
| Make necessary |
|
|
|
|
| outdoor unit PCB OFF? | ||
corrections |
| Refer to “Table of |
| ||||||||
|
|
|
| ||||||||
pin (CN51) on the outdoor unit PCB |
|
|
|
|
|
| |||||
|
|
| Description of Alarm Displays.” |
| YES | ||||||
for 1 second or longer, |
| Turn OFF the indoor |
| ||||||||
|
|
|
|
| |||||||
then release it. |
| and outdoor unit |
|
|
|
|
|
|
|
*3 |
| *3 |
Start indoor and outdoor unit | Start indoor and outdoor unit | |
cooling operation. | heating operation. | |
LED 1 and 2 blink alternately. | LED 1 and 2 blink alternately. |
Are LEDs 1 and 2 on the | NO |
| |
outdoor unit PCB OFF? |
|
YES
Check the alarm
contents.
*2 A minimum of 5 hours must have passed after the power was turned ON to the outdoor unit.
*3 All indoor units operate in all refrigerant systems where the power is ON.
Check that test run preparation is OK.
(Do not allow the
Set the wired remote controller for test run.
Refer to the remote |
|
| NO | |
|
| |||
controller |
|
| ||
Does system operate? | ||||
settings. | ||||
|
|
|
Check and make corrections according to “Table of
YES
Return remote control to normal mode
End test run.
Fig.
69