Possible cause of malfunction |
|
| Alarm | ||
|
| message | |||
Serial | Improper setting. | This alarm message shows when the indoor unit for | L02 | ||
| is not connected to the outdoor unit. |
| |||
|
|
| |||
errors |
| Duplication of main indoor unit address setting in group control. | <L03> | ||
|
|
|
| ||
| Duplication of outdoor R.C. address setting. | L04 | |||
|
| ||||
|
|
|
|
| |
|
| There are 2 or more indoor units | Priority set remote controller | L05 | |
|
| controllers which have operation |
|
| |
|
| L06 | |||
|
| mode priority in 1 refrigerant circuit. | |||
|
| Group control wiring is connected to individual control indoor unit. | L07 | ||
|
|
|
|
| |
|
| Indoor unit address is not set. |
| L08 | |
|
|
|
|
| |
|
| Capacity code of indoor unit is not set. | <<L09>> | ||
|
|
|
| ||
|
| Capacity code of outdoor unit is not set. | L10 | ||
|
|
|
| ||
|
| L17 | |||
|
| of refrigerant. |
| ||
|
|
|
| ||
|
|
|
|
| |
|
|
| L18 | ||
|
|
|
| ||
Activation of | Protective device in indoor unit | Thermal protector in indoor unit fan motor is activated. | <<P01>> | ||
protective | is activated. |
|
|
| |
Improper wiring connections of ceiling panel. | <<P09>> | ||||
device |
| ||||
|
|
|
| ||
| Float switch is activated. |
| <<P10>> | ||
|
|
| |||
|
|
|
| ||
|
| Operation of protective function of fan inverter. | P12 | ||
|
|
|
| ||
|
| O2 sensor (detects low oxygen level) activated. | P14 | ||
|
|
|
| ||
| Protective device in outdoor unit | Compressor thermal protector is activated. | P02 | ||
| is activated. | Power supply voltage is unusual. (The voltage is more than 260 V | |||
|
| or less than 160 V between L1 and L2 phase.) |
| ||
|
| Incorrect discharge temperature. |
| P03 | |
|
|
|
|
| |
|
| High pressure switch is activated. |
| P04 | |
|
|
|
| ||
|
| Detective phase | P05 | ||
|
|
|
| ||
|
| Compressor running failure resulting from missing phase in the | P16 | ||
|
| compressor wiring, etc. (Start failure not caused by IPM or no gas.) | |||
|
|
| |||
|
|
|
|
| |
|
| Outdoor unit fan motor is unusual. |
| P22 | |
|
|
|
| ||
|
| Overcurrent at time of compressor runs more than 80Hz (DCCT | P26 | ||
|
| secondary current or ACCT primary current is detected at a time | |||
|
| other than when IPM has tripped.) |
|
| |
|
|
|
|
| |
|
| IPM trip (IPM current or temperature) | H31 | ||
|
|
|
| ||
|
| Inverter for compressor is unusual. (DC compressor does not | P29 | ||
|
| operate.) |
| ||
|
|
|
| ||
Thermistor | Indoor thermistor is either open | Indoor coil temp. sensor (E1) |
| <<F01>> | |
fault | or damaged. |
|
|
| |
Indoor coil temp. sensor (E2) |
| <<F02>> | |||
|
|
| |||
|
|
|
|
| |
|
| Indoor coil temp. sensor (E3) |
| <<F03>> | |
|
|
|
| ||
|
| Indoor suction air (room) temp. sensor (TA) | <<F10>> | ||
|
|
|
| ||
|
| Indoor discharge air temp. sensor (BL) | <<F11>> | ||
|
|
|
|
| |
| Outdoor thermistor is either | Compressor discharge sensor (TD) |
| F04 | |
| open or damaged. |
|
|
| |
| Outdoor No. 1 coil liquid temp. sensor (C1) | F07 | |||
|
| ||||
|
|
|
|
| |
|
| Outdoor air temp. sensor (TO) |
| F08 | |
|
|
|
| ||
|
| Compressor suction port temperature sensor (TS) | F12 | ||
|
|
|
|
| |
|
| High pressure sensor |
| F16 | |
|
|
|
|
| |
EEPROM on indoor unit PCB failure |
|
| F29 | ||
|
|
|
|
| |
Protective | Protective device for compressor | EEPROM on the outdoor unit PCB is a failure. | F31 | ||
device for | No. 1 is activated. | ||||
|
|
| |||
compressor is |
| Current is not detected when comp. is ON. | H03 | ||
activated |
| ||||
|
|
|
| ||
|
|
|
|
|
80